摘要 对某实际受端电力系统进行了机电暂态仿真,表明当受端系统联系紧密时,负荷动态特性对三相短路电流周期分量的初始有效值及其在50 ms内的衰减数值影响较大,对该电网某次三相短路故障录波数据的波形分解结果也支持上述观点。仿真还表明,由于三相短路电流存在衰减,传统的不考虑负荷动态特性时求出的短路电流周期分量初始有效值仍可用来检验断路器的开断能力,但不宜用来检验断路器的动稳定。 Mechanic-electric simulation of a real receiving-end power system shows that the load dynamics have a significant impact on the symmetrical three-phase short-circuit current within 50 ms after short-circuit.This is supported by the fault-recording data of a power grid accident.The simulation data and the fault-recording data both indicate that the result from the traditional practical short-circuit calculation can be used to check the interrupting capacity of the circuit breaker,but can not be used to check the stress intensity of the circuit breaker.
出处 《电力系统自动化》 EI CSCD 北大核心 2011年第5期61-65,共5页 Automation of Electric Power Systems
基金 国家电网公司科技项目(08310531111696)~~
关键词 短路电流 开断电流 冲击电流 动态负荷 故障录波 short-circuit current interrupting current peak current dynamic load fault-recording
  • 相关文献

参考文献7

二级参考文献18

  • 1贺仁睦,魏孝铭,韩民晓.电力负荷动特性实测建模的外推和内插[J].中国电机工程学报,1996,16(3):151-154. 被引量:46
  • 2章健.电力系统负荷建模方法的研究[D].北京:华北电力大学,1997.
  • 3GB1984-2003.高压交流断路器[S].[S].,..
  • 4Dmitry NK, Carson WT, William AM. Model validation for the August 10,1996 WSCC system outage[J].IEEE Transactions on Power Systems, 1999, 14(3): 967-979.
  • 5He Renmu, Ma Jin, David Hill Composite load modeling via measurement approach[J]. IEEE Trans on Power Systems, 2006,21(2): 663-672.
  • 6Ma Jin, He Renmu, David Hill Load modeling by finding support vectors of load dais from field measurements[J]. IEEE Trans on Power Systems, 2006, 21(2): 726-735.
  • 7汤涌,张东霞,朱方,等.东北电网大扰动试验仿真分析[R].北京:中国电力科学研究院,2004.
  • 8SMEETS R P P, ALDROVANDI G, CHEVRIER P, et al. Statistical Analysis of Electrical Stresses on High-voltage Circuit-breakers in Service[J]. ELECTRA, 2005(220): 24-29.
  • 9JANSSEN ALJ,SOLVERCE.用于CIGRE SC A3/WG13.08和IECSC17A/WG29的高压断路器电寿命型式试验的统计数据[C]//CIGRE,2004:A3-30.
  • 10BALZER G,DRESCHER D.高压断路器的故障数据用于评估状态维护[C]//CIGRE,2004:A3-305

共引文献48

同被引文献130

引证文献16

二级引证文献155

相关作者

内容加载中请稍等...

相关机构

内容加载中请稍等...

相关主题

内容加载中请稍等...

浏览历史

内容加载中请稍等...
;
使用帮助 返回顶部