高压直流换流站换流阀开关电磁瞬态特性实验研究 被引量:12

Experimental Research on Switching Electro-magnetic Transient Characteristics of Converter Valves in HVDC Converter Stations
下载PDF
导出
摘要 高压直流换流站中,换流阀开关电磁瞬态是稳态电磁骚扰分析和换流器均压设计的关键考虑因素。因此基于高压换流阀运行实验系统搭建了换流阀开关瞬态特性测量系统,获得了换流阀开通和关断过程中电压、电流瞬态波形,分析了电压、电流和磁场的频率特性,研究了换流阀工作电压、工作电流和结温对开通和关断过程的影响。结果表明,开通过程中电压呈指数变化,开通时间约为数μs;随着工作电压、工作电流和结温的升高,开通时电压下降时间随之上升,变化幅度可达20%以上;关断时间受运行电压、电流、结温的影响不明显,电流增大时,关断过程电压峰值也增大。因此,换流阀瞬态特性分析时,需考虑运行参数对开通和关断过程的影响。 Electromagnetic transient of valves in HVDC converters during turn-on and turn-off processes is the major factor for steady state electromagnetic disturbance(EMD) which is considered in analysis and grading devices design.Consequently,a measuring system for electromagnetic transient research was established.Transient waveforms of voltage across valve,current through it and magnetic field near it were gained during the valve operation.The spectra of voltage,current and magnetic field were analyzed.Influences of operating voltage,current and junction temperature on switching transients were studied.Results show that voltage changes exponentially during turn-on process,and the turn-on time is about several micro seconds.Turn-on time rises with increasing of operating voltage,current and junction temperature,the change amplitudes are up to 20%.Influences of operating voltage and junction temperature on turn-off time are not obvious.Therefore,the influences of operating parameters on turn-on and turn-off should be considered.
出处 《高电压技术》 EI CAS CSCD 北大核心 2011年第3期739-745,共7页 High Voltage Engineering
基金 国家自然科学基金(50907036)~~
关键词 高压直流 换流阀 电磁瞬态 开关过程 电磁骚扰 晶闸管 HVDC converter valves electromagnetic transient switching operations electromagnetic disturbance thyristor
  • 相关文献

参考文献23

  • 1Annestrand S A. Radio interference from HVDC converter stations [J]. IEEE Trans on Power Apparatus and Systems, 1972, 91(3): 874-882.
  • 2Maruvada P S, Gilsig T. A Method of Calculating the RI from HVDC Converter Stations[J]. IEEE Trans on Power Apparatus and Systems, 1973, 92(3): 1009-1018.
  • 3Morse A R. Field measurements of station-generated RI on the Nelson river HVDC line in 1976[C]// Proceedings of the International Electrical and Electronics Conference, Toronto, Canada: [s.n.],1977: 78-79.
  • 4Melvold D J , Haglof L, Degn P. Carrier frequency harmonics generated by HVDC conversion[J]. IEEE Trans on Power Apparatus and Systems, 1980, 99(2) : 564-572.
  • 5Bacon G H, Hedrick D L, Fiedler J J, et al. Power line carrier application considerations involving HVDC transmission [J ]. IEEE Trans on Power Apparatus and System, 1980, 99(3): 1089-1096.
  • 6Sebo S A, DeVore R V. Scale model study of RF effects caused by HVDC converter stations[C]// Proceedings of the International Conference on DC Power Transmission. Montreal, Canada:[s, n.], 1984: 184-190.
  • 7Caldecott R, DeVore R V, Kasten D G, et al. HDVC converter station tests in the 0.1 to 5 MHz frequency [J]. IEEE Trans on Power Delivery, 1988, 3(3): 971-977.
  • 8YU Zhan-qing, HE Jin-liang, ZENG Rong, et al. Simulation analysis on conducted EMD caused by valves in ±800 kV UHVDC converter station [J]. IEEE Trans on EMC, 2009, 51(2) : 236-244.
  • 9YU Zhan-qing, HE Jin-liang, ZENG Rong, et al. Simulation analysis on radiated EMI from the DC buses in ± 500 kV HVDC converter stations[C]// Proceedings of 18th International Zurich Symposium on Electromagnetic Compatibility. Mtinchen, Germany: [s. n.], 2007: 357-360.
  • 10YU Zhan-qing, HE Jin liang, ZENG Rong, et al. Simulation analysis on EMI of ±800 kV UHVDC converter station【C]// Proceedings of 2007 IEEE International Symposium on Electro magnetic Compatibility (IEEE EMC 2007). Hawaii, USA: IEEE, 2007: 1288-1292.

二级参考文献92

共引文献141

同被引文献192

引证文献12

二级引证文献138

相关作者

内容加载中请稍等...

相关机构

内容加载中请稍等...

相关主题

内容加载中请稍等...

浏览历史

内容加载中请稍等...
;
使用帮助 返回顶部