期刊文献+

天伦王朝饭店暖通空调设计 被引量:4

Air conditioning design of the TianLun Dynasty Hotel
下载PDF
导出
摘要 介绍了该饭店空调、供暖、防排烟系统设计,特别是中庭的空调设计。饭店的中庭高23 m ,采用分层空调方式,在6 m 高处设送风喷口向下送风,由大厅下部回风,既可满足人员活动区的舒适要求,又节省了运行费用。实测结果表明,满足设计要求。 Presents the air conditioning, heating, smoke control system design of the hotel, especially those for the atrium which is 23 meters high, with supply air nozzle outlets at a level of 6 meters high and return air louvers in lower part of the side wall. By this way, it not only meets comfort requirements in the occupant zone, but also saves the running expense. Results by measurement indicate that the system works well as designed. Points out issues to be carefully considered including the load calculation of the inner zone and cooperation of all disciplines.
作者 陈连仲
出处 《暖通空调》 北大核心 1999年第6期50-52,共3页 Heating Ventilating & Air Conditioning
关键词 暖通空调 设计 中庭 节能 饭店 HVAC design, atrium, energy conservation, experience