期刊文献+

振荡波电压法检测10kV电缆局部放电试验 被引量:25

10 kV XLPE cable partial discharge detection based on oscillating waves
下载PDF
导出
摘要 介绍了振荡波电压法测试系统的主要原理、设备构成及局部放电定位技术的原理;基于振荡波电压法检测技术,通过在一条退运10 kV交联聚乙烯短电缆上人工设置各种模拟缺陷,对系统的检测效果进行了初步分析,得出振荡波电压法对某些类型的缺陷如错用绝缘胶带等效果十分明显,而对其他一些缺陷如压接管表面存在毛刺等效果有待进一步研究;研究也表明电缆终端缺陷的检测可能会由于高压线夹表面放电引入干扰受到影响,建议采取其他辅助检测手段如开关柜局部放电检测技术或对高压线夹进行防电晕处理。 The composition of OWTS(Oscillating Wave Test System) and the principle of PD(Partial Discharge)locating technique are introduced.A short XPLE cable which is out of service is artificially set with various simulative defects and tested by OWTS.The results of tests show that,some defects are easily detected,such as the misuse of insulating tape,but the others are not,such as the surface burr of press-connect-tubes.Study shows that the detection of terminal defect may be influenced by the surface discharge of high-voltage line nipper and the switchgear PD detecting technology or the anti-corona treatment of high-voltage line nipper is suggested.
出处 《电力自动化设备》 EI CSCD 北大核心 2010年第11期137-140,共4页 Electric Power Automation Equipment
关键词 配网 电缆 振荡波 局部放电 distribution system cable oscillating wave partial discharge
  • 相关文献

参考文献11

  • 1罗俊华,邱毓昌,杨黎明.10kV及以上电力电缆运行故障统计分析[J].高电压技术,2003,29(6):14-16. 被引量:195
  • 2GULSKI E,WESTER F J,SMIT J J. Advanced partial discharge- diagnostic of MV power cable system using oscillating wave test system[J]. IEEE El Magazine,2000,16(2) : 17-25.
  • 3罗俊华,马翠姣,邱毓昌,金祎,陈守直,史济康.35kV及以下XLPE电力电缆试验方法的研究[J].电网技术,2000,24(12):58-61. 被引量:62
  • 4UCHIDA K,TANAKA H,HIROTSU K. Study on detection for the defects of XLPE cable lines[J]. IEEE Transactions on Po- wer Delivery, 1996,11 (2) :663-668.
  • 5GULSKI E,WESTER F J,SMIT J J,et al. PD knowledge rules for insulation condition assessment of distribution power cables[C]//5th Volta Colloquium on Partial Discharge Measurement, PD Measurements in the Field. Alkmaar,Netherlands:[s.n.], 2005 : 1-9.
  • 6TURNER M. A new method for diagnosis of installed medium voltage power cables[R/OL]. (2006- 12-20) [2010-07-06]. http ://kth.diva-portal.org/smash/get/diva2:9062/FULLTEXT01.
  • 7PETZOLD F,GULSKI E,SEITZ P P,et al. Advanced solution for on-site diagnosis of distribution power cables[C ]//2008 International Conference on Condition Monitoring and Diagnosis. Beijing,China : [s.n.],2008: 1-4.
  • 8GULSKI E,CICHECKI P,SMIT J J,et al. 0n-site condition moni- toring of HV power cables up to 150 kV[C]//2008 Interna- tional Conference on Condition Monitoring and Diagnosis. Bei- jing, China: [s.n. ],2008:978-982.
  • 9GULSKI E,PIEPERS O,PETZOLD F,et al. Power cables con- dition indexing by statistical analysis of diagnostic data[R/OL]. (2005-12-27) [2010 -07-06]. lattp: /'/journals.|ww.com / investigativeradiology / Abstract / 1989 / 03000 / Some_Practical_Is- sues_ofExperimental_Designand. 12.aspx.
  • 10杨荣凯.XLPE电缆线路局部放电量指标的分析[J].高电压技术,2005,31(2):27-28. 被引量:11

二级参考文献11

  • 1罗俊华,袁淳智.XLPE电力电缆在直流电场下介质树枝状劣化特性的研究[J].高电压技术,1993,19(1):41-46. 被引量:15
  • 2Junhua Luo, et al. Study on surface discharge of composite dielectric in XLPE power cable joints[A]. 25th Anniversary Electrical Insulation Conference [ C ].Cincinnati, USA, 2001.
  • 3IEC60502.额定电压1 kV(Um=1.2 kV)至30 kV(Um=36 kV)挤包绝缘电力电缆及附件[S].[S].,1997..
  • 4IEC60840.额定电压36 kV(Um=36 kV)以上至150 kV(Um=170 kV)挤包绝缘电力电缆及附件试验方法和要求[S].[S].,1999..
  • 5IEC62067.额定电压150 kV(Um=170 kV)以上至500 kV(Um=550kV)挤包绝缘电力电缆及附件试验方法和要求[S].[S].,2001..
  • 6GB/T12706.额定电压1 kV(Um=1.2 kV)到35 kV(Um=40.5 kV)挤包绝缘电力电缆及附件[S].[S].,2002..
  • 7GB/T11017.额定电压110 kV交联聚乙烯绝缘电力电缆及其附件[S].[S].,2002..
  • 8GB/Z18890.额定电压220 kV(Um=252 kV)交联聚乙烯绝缘电力电缆及其附件[S].[S].,2002..
  • 9李祥忠.0.1Hz下电缆介损测量技术的进展[J].广东电力,1998,11(3):8-9. 被引量:7
  • 10史济康,曹家,袁检,罗俊华,胡文康.XLPE电力电缆中间接头复合介质沿面放电研究[J].高电压技术,2001,27(4):52-53. 被引量:50

共引文献253

同被引文献195

引证文献25

二级引证文献197

相关作者

内容加载中请稍等...

相关机构

内容加载中请稍等...

相关主题

内容加载中请稍等...

浏览历史

内容加载中请稍等...
;
使用帮助 返回顶部