一起主变、母差保护相继动作原因分析 被引量:8

Analysis of successive trips of transformer differential relay and bus differential relay
下载PDF
导出
摘要 针对一起变电站的110 kV母差保护和220 kV主变保护相继动作跳闸事件展开了分析,通过事故调查发现其存在2个实际故障点,分别位于110 kV母差保护动作区,以及110 kV母差和220 kV主变保护动作的重叠区。当第1次故障发生时,110 kV母差保护动作跳开101断路器;第2次故障导致主变A柜差动保护动作,B柜110 kV复合电压过流保护动作,跳开主变三侧断路器。从继电保护设计的角度出发,对提高继电保护动作可靠性提出了建议。 A substation successive trip event of 110 kV bus differential relay and 220 kV transformer differential relay is described in detail.Investigation shows that two fault points are located respectively in the 110 kV bus relay operation zone and the overlap operation zone of bus relay and transformer relay.For the first fault,the 110 kV bus relay trips breaker 101;for the second fault,both the differential relay A and the 110 kV over-current relay B of main transformer operate to trip the transformer breakers at three sides.Suggestions are proposed to improve the reliability of relay operation.
作者 叶远波 陈实
出处 《电力自动化设备》 EI CSCD 北大核心 2010年第11期146-148,共3页 Electric Power Automation Equipment
关键词 母线差动保护 主变差动保护 拒动 误动 复合故障 bus differential relay transformer differential relay refuse-to-operate misoperation composite fault
  • 相关文献

参考文献7

二级参考文献18

  • 1沈国荣,隋凤海,陈涛,叶锋.LFP—901型超高压线路成套快速保护装置[J].电力系统自动化,1993,17(6):52-56. 被引量:10
  • 2孙志杰,曾献华,汤汉松,吉晨.磁通制动原理在变压器差动保护中应用[J].电力自动化设备,2005,25(1):79-81. 被引量:24
  • 3洪佩孙.电力系统距离保护[M].北京:中国电力出版社,1988..
  • 4叶远波.超高压串补线路继电保护的研究:硕士学位论文[M].南京:河海大学,1998..
  • 5赵振宇 徐用懋.模糊理论和神经网络的基础与应用[M].北京,南宁:清华大学出版社,广西科学技术出版社,1997.105-106.
  • 6王广延.电力系统元件保护基础[M].水利电力出版社,1986..
  • 7王维俭.大机组继电保护基础[M].水利电力出版社,1989..
  • 8李家庭 徐建政.标识式突变电继电器的研究.电力系统自动化第十届年会论文集[M].,1994..
  • 9潘和勋 张军文.电力系统继电保护配置及整定计算[M].成都科技大学电力工程系、四川电力调度局,..
  • 10许继集团.发电机、变压器组微机保护技术说明书[Z].,..

共引文献21

同被引文献41

引证文献8

二级引证文献2

相关作者

内容加载中请稍等...

相关机构

内容加载中请稍等...

相关主题

内容加载中请稍等...

浏览历史

内容加载中请稍等...
;
使用帮助 返回顶部