摘要 对以R410A为制冷剂的水源热泵空调机组进行了变进水温度运行的试验研究。制冷工况进水温度为21~36℃的范围内,制热工况在进水温度在6-21℃的范围内,进行了机组制冷量、制热量、输入功率、EER/COP、吸气和排气压力、压比、吸气和排气温度等特性随进水温度变化的测试,分析了R410A机组在变进水温度下制冷和制热运行的特性,实验研究结果表明在目前极力推广使用的地源热泵空调机组(水源热泵空调机组的一种)中,如果地源埋管系统设计不合理,不仅不节能而且更耗能,且在制冷运行时更为明显。本文为R410A水源热泵空调机组的设计与工程应用提供了试验参考依据。 The performance of a R410A water-source heat-pump was studied experimentally with varied inlet-water tempera-ture.Heating capacity,cooling capacity,power input,EER/COP,discharge pressure,suction pressure,pressure ratio,dischargetemperature,suction temperature,condensing temperature and evaporating temperature were measured in the heating conditions inlet-water temperature of 21℃ ~ 36℃ and cooling conditions inlet-water temperature of 6℃ ~ 21℃.The performance of water-source heat pump at varied inlet-water temperature was analyzed,which provides an important experimental reference to the design and application of units with refrigerant R410A.
机构地区 上海理工大学
出处 《流体机械》 CSCD 北大核心 2011年第3期52-57,共6页 Fluid Machinery
关键词 R410A 水源热泵 变进水温度 R410A water-source heat pump varied inlet-water temperature
  • 相关文献

参考文献10

二级参考文献32

  • 1胡俊伟,丁国良.开缝翅片压降和换热特性的数值模拟[J].上海交通大学学报,2004,38(10):1639-1642. 被引量:25
  • 2刘建,丁国良.以R410A为工质的空调换热器性能仿真与实验[J].上海交通大学学报,2006,40(2):262-266. 被引量:14
  • 3Man-Hoe Kim, Clark W Bullard. Dynamic Characteristics of a R410A Split Air-Conditioning System. Int. J. of Refrig., 2001, 24:652-659.
  • 4Payne W V, Domansi P A. A Comparison of an R22 and an R410A Air Conditoner.Operating at High Ambient Temperatures. In: Proceedings of the 9th International Refrigeration Conference at Purdue. Paper R2-1.
  • 5Motta S F Y, Domanski P A. Performance of R22 and Its Alternatives Working at High Outdoor Temperatures. In: Proceedings of the 8th International Refrigeration Conference at Purdue. 47-54.
  • 6Martinez-Frias J,Aceves S M.Effects of evaporator frosting on the performance of an air-to-air heat pump[J].ASME J.Energy Res.Technol.,1999,121 (1):60-65.
  • 7Guo X M,Chen Y G,Wang W H,et al.Experimental study on frost growth and dynamic performance of air source heat pump system[J].Applied Thermal Engineering,2008 (In Press).
  • 8Kim M H,Clark W.Dynamic characteristics of a R410A split air-conditioning system[J].Int.J.of Refrig.,2001.
  • 9Guo X M,Yang B,Wang W H,et al.Experimental study of interaction between frost growth on evaporator and dynamic characteristics of an air source heat pump[C].Beijing:Proceedings of 22th Int.Congress of Refrig.,2007.
  • 10Nitheanandan T,Soliman H M,Chant R E.A proposed approach for correlating heat transfer during condensation inside tubes[J].ASHRAE Trans.,1990,96(1):230-241.