期刊文献+

大型发电机微机失步保护的研究 被引量:7

STUDY ON MICROPROCESSOR-BASED OUT OF STEP PROTECTION FOR LARGE GENERATOR UNITS
下载PDF
导出
摘要 为克服间接反映发电机功角的传统失步保护所存在的问题,介绍了一种利用发电机调速系统来直接测量发电机功角的方法。提出了利用微机实现此方法的算法,并对此算法的精度进行了数字仿真分析,给出了算法所带来的误差,表明这种算法精度较高。基于此方法实现的大型发电机微机失步保护与传统的失步保护相比,物理概念明确,并且对失步的判别更加精确。目前,基于此方法的新型微机发电机失步保护已在研制之中。 In order to avoid the problems caused by traditional out of step protections based on indirect measurement of power-angle. this paper presents a direct method to measure power-angle of generator by using speed control system and puts forward the algorithm to realize it by using microprocessor. Then the algorithm's accuracy and its error, are investigated by simulation and the results are presented in detail. which show that the algorithm has high accuracy and clear concept. The out of step protection for large generator based on this method is simpler and more accurate than that based on traditional method. Presently, the new out of step protection system is being developed.
出处 《电力系统自动化》 EI CSCD 北大核心 1999年第22期24-27,共4页 Automation of Electric Power Systems
关键词 失步保护 微机保护 大型发电机 继电保护 power-angle oscillation out of step protection microprocessor-based protection
  • 相关文献

参考文献6

  • 1王增平,高中德,毕天姝,柳焯.基于能量原理的新型发电机失步预测及失步保护的研究[J].电力系统自动化,1997,21(11):35-38. 被引量:8
  • 2(日)上之园新佐.同步发电机失步预测控制装置的研制[J].继电器,1982,3(2):55-59.
  • 3王增平,电力系统自动化,1997年,21卷,11期,35页
  • 4王维俭,电气主设备继电保护原理与应用,1996年
  • 5陈德树,计算机继电保护原理与技术,1992年
  • 6李玉海(译),继电器,1982年,3卷,2期,55页

二级参考文献3

  • 1李莉,电力自动化设备,1990年,2期
  • 2徐勇生,电力自动化设备,1989年,3期
  • 3王维俭,大型机组继电保护理论基础(第2版),1989年