期刊文献+

单端行波测距新算法的研究 被引量:2

Research of on a new single terminal Fault Location Algorithm
下载PDF
导出
摘要 传统的单端测距算法需要考虑时间和行波波速两个因素,本文在原有的单端测距算法的基础上消去了行波波速参数,提出了一种不受行波波速影响的的单端测距新算法,与之前的单端行波测距算法相比该算法不受行波波速的影响的优点,而且计算方便、精确。经过ATP对该算法进行仿真验证,仿真结果证明了该算法的实用性。用该算法在超高压长距离输电线路测距误差可以保持在400m以内,更好的满足了电网的可靠运行要求。 The traditional single-ended locating algorithm needs to consider that the time and the traveling wave velocity,the algorithm of this paper has eliminated the traveling wave velocity on the foundation of original single-ended locating algorithm,a new single-ended locating algorithm which is not affected by traveling wave velocity is presented,the impact of traveling wave velocity is excluded comparing with the previous singleended fault location algorithm,this algorithm is convenient,accurate.The utility of this algorithm has been verified by the ATP simulation results.The location algorithm is with error no more than 400m in EHV.Traveling wave velocity long transmission lines,It can satisfy the requirement of power grids operation better.
出处 《东北电力大学学报》 2011年第1期48-51,共4页 Journal of Northeast Electric Power University
关键词 单端故障测距 行波 故障距离 Single-end fault location Traveling wave Fault distance
  • 相关文献

参考文献5

  • 1葛耀中.继电保护和故障测距的原理与技术(第二版)[M].西安:西安交通大学出版社,2007:181-240.
  • 2Jamali S.,Ghezeljeh A..Fault Location On Transmission Line Using High Frequency Travelling Waves[J].The Institution of Electrical Engineers,2004,1 (5 -8):220 -223.
  • 3Ngu Eng Eng,Krishnathevar Ramar.Single-End Traveling Wave Based Fault Location on Two Terinal Transmission Lines[C].2009 IEEE Region 10 Conference,2009:1 -4.
  • 4郑州,吕艳萍,王杰,吴凡.基于小波变换的双端行波测距新方法[J].电网技术,2010,34(1):203-207. 被引量:82
  • 5覃剑,陈祥训,郑健超,吴成琦.利用小波变换的双端行波测距新方法[J].中国电机工程学报,2000,20(8):6-10. 被引量:184

二级参考文献22

共引文献248

同被引文献11

引证文献2