对10 kV架空线路和传统的配电房接地方式所存在的各类问题进行归类分析,并提出改进方法。理论计算和实际使用证明,用混凝土钢筋作为自然接地体,性能优于普通的人工接地体,并且解决了施工方面的困难。
Through the classified analysis of various problems of the traditional grounding methods for 10 kV overhead line and distribution room,this paper provides the improvement methods.After theoretical calculation and practical application,better performance is achieved with the concrete reinforcing steel bar used as the natural grounding body than the common artificial grounding and it overcomes the difficulties in construction.
出处
《浙江电力》
2011年第4期38-41,共4页
Zhejiang Electric Power
关键词
架空线路
配电房
接地
改进
overhead line
distribution room
grounding
improvement