摘要
采用缺氧/MBR/C lO2消毒工艺处理医院废水,当进水COD、BOD5、SS、NH3-N、粪大肠杆菌的平均浓度分别为,219.6mg/L、109.3 mg/L、98.6 mg/L、29.8 mg/L,10000个/L,出水水质优于医疗机构污水排放标准(GB18466-2005)的要求。
The combined process of anaerobic,MBR and ClO2 disinfection was used to treat general hospital sewage.When the average concentrations of the influent COD,BOD5,SS,NH3-N and fecal coliform where 219.6 mg/L,109.3 mg/L,98.6 mg/L,29.8 mg/L and 10000 cfu/L,respectively,the effluent quality was better than the effluent standards of medical institutions(GB18466-2005).