期刊文献+

双馈感应式风力发电系统低压穿越能力仿真研究 被引量:5

Simulation Study of Low Voltage Ride Through Capability for Doubly-fed Wind Turbine Induction Generator
下载PDF
导出
摘要 在电网故障条件下,风电并网导则要求风电发电机具备低压穿越能力。为了保护发电机及其变流器,双馈式感应风力发电机(英文缩写DFIG),需要采用Crowbar保护电路为转子过电流提供旁路通道,同时抑制直流母线过电压。文章介绍了在PSCAD平台下搭建的2MW双馈感应式风力发电系统,并对有无Crowbar电路的DFIG在三相短路条件下进行了仿真。结果表明:具备Crowbar电路的DFIG有较好的暂态特性,并且具备较强的低电压穿越能力。 The standards of wind farm integration into power system required wind turbines in the nature of low voltage ride through capability under grid faults.For protecting generators and converters,The DFIG had to adopt crowbar circuit to bypass rotor over current and suppress DC busbar over voltage.In this paper,2MW DFIG system under PSCAD was constructed.Simulation under the condition either with crowbar circuit or without it was performed sparatcly under three-phase short-circuit.The result indicated that the DFIG equipping with crowbar circuit had better transient process characteristic and stronger low voltage ride through capability.
作者 郑斌 张新燕
机构地区 新疆大学
出处 《电机技术》 2011年第2期38-41,共4页 Electrical Machinery Technology
基金 国家自然基金课题(50767003)
关键词 双馈感应式风力发电机 低压穿越 CROWBAR电路 暂态特性 Doubly-fed induction generator Low voltage ride through Crowbar circuit Transient process characteristic
  • 相关文献

参考文献7

  • 1J Morren S W H de Haan. Ride through of Wind Turbines With-doubly-fed Induction Generator during a Voltage Dip[J]. IEEE Trans. on Energy Convers, 2005, 20 (2) : 435-441.
  • 2王伟,孙明冬,朱晓东.双馈式风力发电机低电压穿越技术分析[J].电力系统自动化,2007,31(23):84-89. 被引量:121
  • 3PIWKO R, MILLER N, SANCHEZ-GASCA J. Integrating large wind farms into weak power grids with long transmission, procedlings of Distribution Conference and Exhibitions:Asia and pacific, 2005 (8) : 14-18.
  • 4胡书举,李建林,许洪华.变速恒频风电系统应对电网故障的保护电路分析[J].变流技术与电力牵引,2008(1):45-50. 被引量:25
  • 5梁亮,李建林,许洪华.双馈感应式风力发电系统低电压穿越研究[J].电力电子技术,2008,42(3):19-21. 被引量:36
  • 6Seman S, iiranen J, anerva S, t nalysis of a 1. 7 MVA doublyfed wind-power induction generator during power systems isturbances[C], roceedings ofNORPIE, rondheim, orway, 004.
  • 7Niiranen J. oltage dip ride through of doubly-fed generator equipped with active crowbar[C], e Nordic Wind Power Conference, teborg, eden, 004.

二级参考文献36

共引文献167

同被引文献43

  • 1LEDESMA P, USAOSA J. Doubly fed induction generator model for transient stability analysis [ J ]. IEEE Trans on Energy Conversion,2005,20 (2) : 388 - 397.
  • 2MAGUEED F A,SANNINO A, SVENSSON J. Transient performance of voltage source converter under unbalanced vo!tage dips [ C ]//DRVr 2004. Hong Kong: IEEE,2004 : 1i63 - 1168.
  • 3SUN T, CHEN Z, BLAABJERG F. Voltage recovery of grid-connected wind turbines with DFIG after a short circuit fault [C ]//PESC2004. Xi' an: IEEE, 2004: 20 - 25.
  • 4CHOWDHURY B H, CHELLAPILLA S. Double-fed induction generator control for variable speed wind power generation [ J ], Electric Power Systems Research, 2006, 76(12) :786 - 800.
  • 5SLOOTWEG J G, DE HAAN S W H, POLINDER H, et al. General model for representing variable speed wind turbines in power system dynamics simulations [ J ]. Power Systems, IEEE Transactions on, 2003, 18(1): 144-151.
  • 6内蒙古风电场接入电网规定技术规定[S].
  • 7PRADHAN A K, JOOS G. Adaptive distance relay setting for lines connecting wind farms[J].Energy Con- version IEEE Transactions on, 2007,22 ( 1 ) : 206 - 213.
  • 8岳亮,高亮,周皓,等.风力发电机组接入下的短路故障仿真及保护问题[A].2010 3rd International Conference on Power Electronics and Intelligent Transportation System [C].Shenzhen:IEEE,2010,548 - 551.
  • 9ENAYATI B.Protection of photovoltaic and wind generators [A].Transmission and Distribution Conference and Exposition,2012 IEEE PES [C]. Latin: IEEE, 2012,1-8.
  • 10LEI XIAN GUO,DUAN JIAN DONG .Wind farm tie- line protection setting based on adaptive current-voltage protection principles[A]. Power and Energy En- gineering Conference (APPEEC),2012 Asia-Pacific [C].Shanghai : IEEE, 2012,1-4.

引证文献5