期刊文献+

跨临界CO_2带膨胀机和带喷射器逆循环的性能比较 被引量:9

A performance comparison of the transcritical CO_2 refrigeration cycle with expander and ejector
下载PDF
导出
摘要 摘要:针对跨临界CO2带膨胀机和带喷射器逆循环的差异,从循环工作原理、CO2超临界流体降压过程及循环性能三方面进行对比分析。利用蒸发波理论分析了CO2超临界流体降压过程,结果表明这两个降压过程均是由亚稳态经历蒸发波后发生气液两相流的,其过程均受蒸发波影响。当其他条件相同,气体冷却器出口温度为35℃时,带膨胀机仇为0.7循环的EER最大值比带喷射器肛为0.7循环的EER最大值高24%,而在蒸发温度为5℃时,前者的EER最大值比后者的EER最大值高33%。在比较工况下,跨临界CO2带膨胀机循环在膨胀机绝热效率为30%-70%时的效率普遍高于带喷射器循环在喷射系数为0.3~0.7时的效率。 In this article, a comparative study was performed for the transcritical C02 refrigeration cycles with expander and ejector in three aspects of the working principle of the cycle, the depressurization of supercritical CO2 and performances of the cycle. In the view of the working principle of the cycle, the cycle with expander had great advantage over the cycle with ejector in some aspects of the recovery of throttle loss and the irreversible loss. On the basis of the theory of evaporation waves, the depressurization of supercritieal CO2 was analyzed. The results show that the depressurizations of two cycles both underwent evaporation wave, then produced gas - liquid two - phase flow , and these processes were significantly affected by evaporation waves. When the gas cooler outlet temperature was 35℃ under otherwise identical conditions, the EER of the cycle with the expander efficiencies at O. 7 was better than that of the cycle with the entrainment ratio at 0.7 by above 24%. Whereas, the evaporation temperature was 5℃ under otherwise identical conditions, the former was up to 33% better than the latter. Under the comparative working conditions in this study, cycles with the expander efficiencies at 0.3 - 0.7 overperformed generally cycles with the entrainment ratio at 0.3 - 0.7.
出处 《低温与超导》 CAS CSCD 北大核心 2011年第5期36-41,共6页 Cryogenics and Superconductivity
基金 国家自然科学基金项目(50976057) 高等学校博士学科点专项科研基金课题(20090032110003)资助
关键词 跨临界循环 二氧化碳 膨胀机 喷射器 蒸发波 性能比较 Transcritical cycle, CO2, Expander, Ejector, Evaporation waves, Performance comparison
  • 相关文献

参考文献12

  • 1马一太,王侃宏,杨昭,吕灿仁.带膨胀机的CO_2跨(超)临界逆循环的热力学分析[J].工程热物理学报,1999,20(6):661-665. 被引量:21
  • 2Nickl J, Will G, Quack H, et al. Integration of a three -stage expander into a CO2 refrigeration system[ J]. In- ternational Journal of Refrigeration, 2005, 28 ( 8 ) : 1 219 - 1 224.
  • 3Mitsuhiro Fukuta, Tadashi Yanagisawa , Reinhard Rad- ermacher. Performance prediction of vane type expander for CO2 cycle [ C ]//International Congress of Refrigera- tion, 2003.
  • 4李敏霞,马一太,苏维诚.CO_2跨临界循环水源热泵摆动转子膨胀机样机的研制开发[J].太阳能学报,2008,29(9):1051-1056. 被引量:4
  • 5Elbel S, Hrnjak P, Experimental validation and design study of a trans - critical CO2 prototype ejector system [ C]//The 7th IIR Gustav Lorentzen Conference on Nat- ural Working Fluids ,2006.
  • 6Li Daqing, Groll Eckhard A. Analysis of an ejector ex- pansion device in a transcritical COz air conditioning system[ C]//The 7th IIR Gustav Lorentzen Conference on Natural Working Fluids ,2006.
  • 7Satoshi Akagi, Chaobin Dang, Eiji Hihara. Characteris- tics of pressure recovery in two - stage ejector applied to carbon dioxide heat pump cycle[ C ]//The 9th Interna- tional IEA Heat Pump Conference, 2008.
  • 8邓建强,姜培学,卢涛,卢苇.跨临界二氧化碳蒸气压缩/喷射制冷循环性能比较[J].工程热物理学报,2006,27(3):382-384. 被引量:13
  • 9Hahne E, Barthau G. Evaporation waves in flashing processes[ J]. International Journal of Multiphase Flow, 2000, 26 (4) : 531 - 547.
  • 10管海清.CO2跨临界循环膨胀机理与转子式膨胀机-压缩机研究[D].天津:天津大学,2002.

二级参考文献12

  • 1马一太,管海清,杨俊兰,刘圣春.带引射器和经济器的CO_2跨临界制冷系统[J].工程热物理学报,2005,26(2):189-192. 被引量:4
  • 2邓建强,姜培学,卢涛,王国梁,卢苇.跨临界CO_2蒸气压缩/喷射制冷循环理论分析[J].清华大学学报(自然科学版),2006,46(5):670-673. 被引量:18
  • 3王侃宏,工程热力学与能源利用学术会议论文集,1998年,IV-47-52页
  • 4Lorentzen G. The use of natural refrigerants: a complete solution to the CFC/HCFC predicament[ J]. Int J Refrig, 1995, 18(3) : 190--197.
  • 5Robinson D M, Grol E A. Efficiencies of transcritical CO2 cycles with and without an expansion turbine[J]. Int J Refrig, 1998, 21(7): 577--589.
  • 6Huff H J, Redarmacher R, Marcus Preissner. Experimental investigation of scroll expander in carbon dioxide air conditiong systerm [ A ]. International Congress of Refrigeration [C], Washington D C, USA, 2003, ICR0485.
  • 7Katsumi Sakitani, Michio Moriwaki, Masakazu Okamoto, et al. Development of two-phase flow expander for CO2 heat pump and air-conditioners[A]. Proceeding of International Heat Pump Conference in 2005[C], Las Vegas, USA.
  • 8Fukuta Mitsuhiro, Yanagisawa Tadashi, Radermacher R. Performance prediction of vane type expander for CO2 cycle[ A]. International Congress of Refrigeration[ C ], Washington D C, USA, 2003, ICR0251.
  • 9Baek J S, Groll E A, Lawless P B. Piston-cylinder work producing expansion device in a transcritical carbon dioxide cycle (Part I): Experimental investigation[J]. International Journal of Refrigeration, 2005, 28: 141--151.
  • 10Stosic N, Smith I K, Kovacevic A. Twin screw combined compressors and expanders for CO: refrigeration systems[A]. The Proceeding of the Sixteenth International Compressor Engineering Conference at Purdue[C], 2003.

共引文献36