期刊文献+

示踪技术法检测反应堆堆厅气体渗漏率 被引量:2

Air Leakage Test of Reactor Hall Using Tracer Technique
下载PDF
导出
摘要 采用SF6示踪技术检测某反应堆3个堆厅在常温常压下的气体渗漏率,考察堆厅渗漏气体在主要工作场所的累积效应和到达建筑物内人员疏散通道关键部位的时间和累积强度。结果表明,3个反应堆堆厅在检测条件下的气体渗漏率分别为(7.30±0.16)×10-4、(1.88±0.12)×10-4和(2.07±0.07)×10-4 h-1。堆厅渗漏气体在各工作间以较快速度积累,5h左右在工作间内达到极值,在一楼更衣室内的累积效应明显;堆厅渗漏气体在人员通道的累积幅度较小,约10h达到极值浓度。 The leakage ratios of three related reactor halls were tested by sulfur hexafluoride gaseous tracer technique.Moreover,the accumulation intensities of leak gas and its retention time in some important working rooms,the crossroads of corridors and anteroom of the building were detected.The results show that the air leakage ratios of the three reactor halls are(7.30±0.16)×10-4,(1.88±0.12)×10-4 and(2.07±0.07)×10-4 h-1.The leak gas accumulates in all the detected working rooms fast,and the retention time to various rooms is about 5 h.The heaviest intensities are in the clothes change rooms on the first floor.However,the retention time to the crossroads and the anteroom is about 10 h,and the accumulation intensities are much small.
出处 《原子能科学技术》 EI CAS CSCD 北大核心 2011年第5期582-587,共6页 Atomic Energy Science and Technology
关键词 反应堆大厅 气体渗漏 示踪技术 气体示踪剂 SF6 reactor hall air leakage tracer technique gaseous tracer sulfur hexafluoride
  • 相关文献

参考文献10

  • 1羊衍秋,杨通在,邢丕峰.全氟碳化合物示踪技术及应用[J].气候与环境研究,2003,8(4):485-494. 被引量:22
  • 2RUSSELL N D, EDGAR A C, GUNNAR I S, et al. An inexpensive perfluorocarbon tracer technique for wide-scale infiltration measurements in homes, BNL-30032[R]. US:Brookhaven National Laboratory, 1981.
  • 3RUSSELL N D, EDGAR A C. Air infiltration measurements in a home using a convenient perfluorocarbon tracer techniqiue[J]. Environment International, 1982(8): 419-433.
  • 4SHERMAN M H. Air infiltration measureraent techniques, LBL-27656 [R]. Berkeley, California: Lawrence Berkeley Laboratory, University of California, 1998.
  • 5SHERMAN M H. Uncertainty in air flow calculations using tracer gas measurements, LBL 25415 [R]. Berkeley, California: Lawrence Berkeley Laboratory, University of California, 1998.
  • 6羊衍秋,何玉晖,田杰,姜涛.阀切换技术在大气样品中六氟化硫快速分析中的应用[J].色谱,2007,25(4):609-610. 被引量:10
  • 7ALLWINE K J, LAMB B K, ESKRIDGE R. Wintertime dispersion in a mountainous basin at Roanoke, Virginia: Tracer study[J]. Journal of Applied Meteorology, 1992, 31: 1 296 -1 311.
  • 8DIETZ R N. Gaseous-tracer technology and applications, BNL-33585[R]. US: Brookhaven National Laboratory, 1983.
  • 9王景书,余秀芬,张永义,施艾伟.用示踪气体稀释法测量房间换气速度[J].环境科学,1990,11(4):65-69. 被引量:3
  • 10朱能,田哲,王侃红.示踪气体跟踪测量方法在空调通风上的应用[J].暖通空调,1999,29(2):58-62. 被引量:17

二级参考文献67

  • 1[40]Vincent, A. M. , and R. J. Farber, Relating summer ambient particulate sulfur, sulfur dioxide, and light scattering to gaseous tracer emissions from the MOHAVE Power Project, J. Air & Waste Manag. Assoc. , 2000,50, 746~755.
  • 2[41]Watson, T. B. , R. Johnson, M. L. Pitchford et al, The Perfluorocarbon tracer releases during the Big Bend Regional Aerosol and Visibility Observational (BRAVO) study, http: //www. aqd.nps.gov/ard/bravo/BRAVO _ tracer. release. pdf
  • 3[42]Hales, J. M. , Tracer applications in the California Regional PM2. 5/PM10 air quality study, 1998, http://www. arb. ca. gov/airways/Documents/drafts/report. pdf
  • 4[43]Dugstad, O. , T. Bjoernstad, and I. A. Hundere, Measurements of gas tracer retention under simulated reservoir conditions, J. Pet. Sci. Eng., 1993, 10 (1), 17~25.
  • 5[44]Dietz, R. N. , Commercial applications of perfluorocarbon tracer (PFT) technology, BNL-46265, Upton, NY,Brookhaven National Laboratory, 1991.
  • 6[45]Ledwell J. R. , A. J. Watson, and W. S. Broccher, A deliberate tracer experiment in Santa Monica Basin, Nature, 1986, 323, 322~324.
  • 7[46]Watson, A. J. , M. I. Liddicoat, and J. R. Ledwell, Perfluorodecalin and sulfur hexafluoride as purposeful marine tracers: some deployment and analysis techniques, Deep-Sea Res. , 1987, 34, 19~31.
  • 8[47]Fogelqvist, E. , M. Krysell, and P. Ohman, Evaluation of perfluoromethyldecalin as a deliberate tracer for the study of water mixing process, Marine Chem. , 1989, 26, 339~349.
  • 9[48]Jin, M. , M. Delshad, V. Dwarakanath et al, Partitioning tracer test for detection, estimation and remediation performance assessment of subsurface nonaqueous phase liquids, Water Resour. Res. , 1995, 31, 1201~ 1210.
  • 10[49]Deeds, N. E. , D. C. McKinney, and G. A. Pope, Vadose zone characterization at a contaminated field site using partitioning interwell tracer technology, Environ. Sci. Technol. , 1999, 33, 2745~2751.