摘要
现有规程推荐的方法不适合于同杆双回线路防雷计算,故介绍了用EMTP和电气几何模型计算的三峡500kV 同杆双回线路耐雷水平的结果,并提出降低雷击跳闸率及其危害的措施。
The methode in the existing standard is not suitable to calculate the lightning performance on the double circuit transmission lines. THis paper gives the results on the Three Gorges’500kV double circuit transmission lines obtained by EMTP and the EGM, and presents the measures to reduce the lightning strokes and their harm.