高压输电线路参数对计及电晕放电的电场强度的影响 被引量:11

Effect of High-voltage Transmission Line Parameters on the Electric Field Intensity Considering the Corona Discharge
下载PDF
导出
摘要 在传统模拟电荷法的基础上,建立了高压输电线路地面电场强度的计算方法,其中在计算中考虑了计及电晕放电的影响。以750 kV水平排列和紧凑型线路为例,计算了导线表面系数、线路的子导线半径、相间距、导线对地高度、分裂导线数目、分裂间距等对工频电场的影响。仿真结果表明,减小电晕放电对地面电场影响的几种方式中以适当增加导线的表面系数和对地高度效果最为有效。 Based on the traditional charge simulation method, the computation method of electric field intensity of the high-voltage transmission lines taking account the corona discharge was built. In the paper, it is applied in the computation the 750 kV AC transmission lines'ground level electric field, which is in compact arrangement and in the parallel arrangement. The effect factors are including the conductor coefficient, the sub-conductor radius, the phase spacing, the conductor height, the split-conductor number, and the split-conductor spacing. The simulation results showed that increasing the conductor coefficient and the conductor height can reduce the effect of the corona discharge on electric-field intensity.
出处 《高压电器》 CAS CSCD 北大核心 2011年第6期77-82,86,共7页 High Voltage Apparatus
关键词 模拟电荷法 高压输电线路 电晕放电 电场强度 charge simulation method high-voltage transmission line corona discharge electric field intensity
  • 相关文献

参考文献13

  • 1DAWSON T W,CAPUTA K, STUCHLY M & High-resolution organ dosimetry for human exposure to low-fequency electric fields[J]. IEEE Trans.Power Del., 1998,13(4) : 366-373.
  • 2ANIS H I,ATFIA H,MAHDI A.Statistical modeling of exposure to power line electric fields[J]. Environ. Technol. 1991,12(11):973-983.
  • 3KING R W P.A review of analytically determined electric fields and currents induced in the human body when exposed to 50-60 Hz electromagnetic fields[J]. IEEE Trans. Antennas Propagat, 2004,52(5) : 1186-1192.
  • 4KING R W P,WU T T.Currents and electric fields induced in the human body when the arms are raised[J]. Journal of Applied Physics, 1997,81(11):7116-7128.
  • 5俞集辉,张剑,张淮清,郝战铎.交流输电线电晕放电对地面工频电场影响的简便计算方法[J].高电压技术,2010,36(5):1228-1233. 被引量:8
  • 6郑亚利,俞集辉,汪泉弟,邹志星,田甜.电晕放电对超高压输电线路工频电场的影响[J].高电压技术,2009,35(4):872-876. 被引量:31
  • 7ABDEL SALAM M,ABDEL AZIZ E Z.Improved calculation for corona loss on three-phase power transmission lines[C]// Industry Applications Society Annual Meeting.USA:IEEE, 1994 : 1601-1607.
  • 8ABDEL SALAM M ,ABDEL AZIZ E Z.A charge simulation 2 based method for calculating corona loss on AC power transmission lines[J]. J Phys D:Appl Phys,1994, 27(4): 2570-2579.
  • 9SALAM A.Computation of ion2 flow fields of AC coronating wires by charge simulation techniques[J]. IEEE Transactions on Electrical Insulation, 1992,27 (2) : 352-361.
  • 10李伟,张波,何金良,曾嵘,黎小林,王琦.超特高压交流输电线路电晕对地面电场的影响[J].高电压技术,2008,34(11):2288-2294. 被引量:31