期刊文献+

SF_6电气设备塑袋包扎检漏方法误差分析及检漏仪的现场校验 被引量:11

Error Analysis of Leak Detection Method for SF_6 Electrical Equipmen's Packaging with Plastic Bags and the Detector's On-site Calibration
下载PDF
导出
摘要 工厂内及安装现场检查SF_6组合电气设备气体密封性能一般采用塑袋局部封装包扎检漏方法,影响该检漏方法结果的因素较多,环境温度、气压、包扎塑袋体积测估以及检测仪器的误差等均会影响检测结果,按文中讨论的方法加以注意和控制,可将检漏检验误差控制在±50%以内。 For inspection of SF6 leakage at factory and installation spot,the general method is local packaging with plastic bags for GIS. There're many factors that can affect the result of this method,for example, environmental temperature, atmosphere pressure, volume of plastic bags estimating and the detector's error etc. But if the inspector paid attention to the problems and controlled according to the method of this essay, then the error of the leakage inspection can be controlled within ± 50% or less.
作者 辛夫 吴雪峰
出处 《高压电器》 CAS CSCD 北大核心 2011年第6期83-86,共4页 High Voltage Apparatus
关键词 漏气率 年漏气率 误差 现场比对校验 leak rate annual leak rate error on-site comparison calibration