摘要
按电力行业标准,110kV电网继电保护必须采用远后备原则。对两种接线方式的距离阻抗元件运行特性进行了详细分析,通过具体试验,验证了用110kV线路保护接地距离Ⅲ段适合作为本线路末端变压器相间故障的远后备。
According to electric power system standard, remote backup protection must be provided in 110 kV electric power networks. This paper discusses the operating behavior of impedance element connected in two different modes in detail. Through test on physical model, the result shows that 110 kV line protections are capable of being remote backup protection for transformers.
出处
《电力系统自动化》
EI
CSCD
北大核心
1999年第16期45-46,51,共3页
Automation of Electric Power Systems