期刊文献+

轴流式送风机现场振动处理实例 被引量:4

An Example of On-spot Handling of Axial FD Fan Vibration
下载PDF
导出
摘要 在对300 MW机组轴流式送风机振动问题的处理过程中,通过解体送风机转子判断送风机振动的原因,振动是因安装问题和对设备的强制运行造成的。在进行转子动平衡解决振动问题时,用三点动平衡法配合确认转子质量不平衡的方向。探讨了当振动分析仪以及经验公式计算出的结果不适用的情况下,利用作图的方法来确认配重量的可行性。 This paper introduces an example of on-spot handling of 300 MW unit axial FD fan vibration.It was found that the vibration was caused by erection problem and forced operation based on the disassembly of the rotor of the FD fan.Three points dynamic balancing method with a vibration analyzer was adopted to estimate the direction of gravity of the rotor so as to solve the vibration.The practicability of using graphing method is discussed in the paper to confirm the balance weight when the empirical equation and vibration analyzer's result were not available.
作者 蒋颂昊
出处 《电站辅机》 2011年第1期29-32,共4页 Power Station Auxiliary Equipment
关键词 机组 运行 送风机 振动 动平衡 现场 处理 过程 power unit operation FD Fan vibration dynamic balance on-spot handling process
  • 相关文献

参考文献3

共引文献5

同被引文献31

引证文献4

二级引证文献11

相关作者

内容加载中请稍等...

相关机构

内容加载中请稍等...

相关主题

内容加载中请稍等...

浏览历史

内容加载中请稍等...
;
使用帮助 返回顶部