期刊文献+

由断路器跳跃引起变压器损坏的事故分析及其改进措施

Analysis and Improvement of Accident for Transformer Caused by Circuit Breaker’s Jumps
下载PDF
导出
摘要 叙述了发电厂出线断路器由于液压机构原因发生多次跳跃,使变压器烧损的事故过程及原因,并就该过程对线路重合闸/手合后加速保护、断路器三相位置不一致保护、失灵保护定值提出了改进意见,讨论了当采用发电机-变压器-线路接线方式时的线路重合闸方式。 Many jumps of the power outlet breaker for the hydraulic mechanism of occurrence were described,which led to the transformer’s burning incidents.For the purposes of the process,the proposed improvements were given for the line reclosing on/hand joint protection after the acceleration,protection of the three-phase circuit breaker position inconsistent,failure protection value,and the type of line reclosing when using the generator-trans-former-line mode was discussed.
出处 《低压电器》 北大核心 2011年第8期58-61,共4页 Low Voltage Apparatus
关键词 断路器 跳跃 变压器 事故分析 改进措施 circuit breaker jump transformer accident analysis improvement measure
  • 相关文献

参考文献4

  • 1DL/T684-1999大型发电机变压器继电保护整定计算导则[S].1999.
  • 2周德才,张保会,赵慧梅.最佳重合闸方案的研究[J].继电器,2005,33(1):28-33. 被引量:14
  • 3葛耀中.在单相自动重合闸过程中判据瞬时故障和永久故障的方法.西安交通大学学报,1984,18(2):23-31.
  • 4王梅义.电网继电保护应用[M].北京:水利电力出版社,2000.