宁德电厂闭冷泵节能优化改造 被引量:1

Energy-saving Optimizing Transformation of Closed Cooling Water Pump in Ningde Power Plant
下载PDF
导出
摘要 通过对宁德电厂闭冷水泵进行诊断测试,发现选型裕量太大,扬程偏高,泵效率达不到设计要求,运行工况远离设计工况,制造工艺欠佳,流道对称差。后经过叶片进出口叶型优化、叶轮轴面流道型线优化、叶轮整体流道的优化、提高检修安装工艺等方法,消除了管道振动,降低了厂用电率,实现了节能降耗的目的。 The closed cooling water pump in Ningde plant is tested,the results show that selection margin is too large,pump head is higher,and pump efficiency can't reach the design requirements,operating conditions away from design conditions,manufacturing processes is poor and flow symmetric is difference.Some methods,such as optimizing the leaf blade of import and export,optimizing the impeller shaft type line,optimizing the overall flow of the impeller,and improving maintenance installation process,are used to eliminate the vibration of pipe and reduce the power consumption rate in order to achieve the energy saving purposes.
作者 张旭东
出处 《能源研究与管理》 2011年第2期80-82,85,共4页 Energy Research and Management
关键词 闭冷泵 节能 优化 closed cooling pump energy-saving optimization
  • 相关文献

参考文献4

  • 1A.J斯提潘诺夫(美).离心泵与轴流泵[M].北京:机械工业出版社,1980.
  • 2邹节廉.火电厂节能途径和措施.水泵技术,1983,(1).
  • 3A.A洛马金(苏联).离心泵与轴流泵[M].北京:机械工业出版社,1978.
  • 4A.T特罗斯科兰斯基(波兰).S.拉扎尔基维茨.叶片设计与结构[M].耿慧彬译.北京:机械工业出版社,1981.