期刊文献+

ATSE核心参数选择几点思考 被引量:5

Several Considerations on Selection of ATSE Core Parameters
下载PDF
导出
摘要 提出电气设计中选择ATSE时,应按正常使用时的负荷情况考虑使用类别;根据负荷特性和ATSE在整个供配电系统中的位置选择转换类型及转换时间;在短路时按照PC、CC、CB级分别考虑其短路特性。 When selecting ATSE in electrical design,utilization category should be considered according to the load in normal operation.Transfer type and transfer time should be selected according to load characteristic as well as the location of ATSE in the whole power supply and distribution system.The short-circuit characteristic of ATSE should be considered separately based on PC,CC,CB class in case of short circuit.
作者 宋涛 孙牧海
出处 《建筑电气》 2011年第6期25-29,共5页 Building Electricity
关键词 ATSE 核心参数 使用类别 转换类型 短路特性 ATST core parameter Utilization category Transfer type Short-circuit characteristic
  • 相关文献

参考文献11

  • 1International Electrotechnical Commission. IEC 60947 - 6 -1 : 2005 Low-voltage switchgear and eontrolgear -- Part 6-1: Multiple function equipment -- Transfer switching equipment[Sl. Geneva: IEC Central Office, 2005.
  • 2上海电器科学研究所负责起草..GB14048.1-2006/IEC60947-1.2001低压开关设备和控制设备第1部分:总则[S]..北京:中国标准出版社,,2006....
  • 3上海电器科学研究所负责起草..GB14048.2-2008/IEC60947-2.2006低压开关设备和控制设备第2部分:断路器[S]..北京:中国标准出版社,,2009....
  • 4上海电器科学研究所,负责起草..GB14048.3-2002/IEC60947-3.2001低压开关设备和控制设备第3部分:开关、隔离器、隔离开关及熔断器组合电器[S]..北京:中国标准出版社,,2002....
  • 5上海电器科学研究所,负责起草..GB14048.4-2003/IEC60947-4-1.2000低压开关设备和控制设备第4部分:机电式接触器和电动机起动器[S]..北京:中国标准出版社,,2003....
  • 6上海电器科学研究所,负责起草..GB14048.11-2008低压开关设备和控制设备第6-1部分:多功能电器转换开关电器[S]..北京:中国标准出版社,,2009....
  • 7中国建筑东北设计研究院,JGJ16-2008民用建筑电气设计规范[S].北京:中国建筑工业出版社,2008.
  • 8李炳华.再析自动转换开关电器ATSE可靠性[J].智能建筑电气技术,2006,5(2):84-87. 被引量:1
  • 9曲德刚,徐建兵.合理选择与使用自动转换开关电器(ATSE)[J].建筑电气,2005,24(1):4-8. 被引量:9
  • 10中国联合工程公司.GB50052-2009供配电系统设计规范[S].北京:中国计划出版社,2010.

共引文献252

同被引文献15

引证文献5

二级引证文献7

相关作者

内容加载中请稍等...

相关机构

内容加载中请稍等...

相关主题

内容加载中请稍等...

浏览历史

内容加载中请稍等...
;
使用帮助 返回顶部