摘要
为了研究不同形状、不同材质的避雷针接闪体的引雷性能,采用雷云板模拟雷云对装有防绕击避雷针的地线放电,统计雷云板对防绕击避雷针的击闪概率,对比分析了不同结构、不同材料防绕击避雷针的接闪性能。试验表明,针形铜避雷针闪络率较环形铜避雷针接闪率更高,引雷效果更优,而针形铜避雷针和针形钢避雷针的接闪性能一致。研究结论对线路雷电绕击的实验室模拟方法以及防绕击措施的改进研究均有参考价值。
In order to study the lightning attracting performances of lightning rods with different structures and materials,and simulating the lightning strike from thundercloud to the grounding line of overhead transmission lines through the flashover from the thundercloud-simulating plate to the lightning rod against shielding failure,this paper counts the rate of flashovers,contrasts the flashover performances of lightning rods with different structures and materials.The simulations show that the flashover rate of acicular copper lightning rod is higher than that of the annular copper lightning rod,and thus the former one has better lightning attracting performance.The acicular copper lightning rod is similar with the acicular steel one in flashover performance,and they have the same lightning attracting effect.These results can be taken as reference to the research of the lightning strike simulation methods in laboratory and the measures against lightning shielding failure.
出处
《南方电网技术》
2011年第2期64-67,共4页
Southern Power System Technology
关键词
避雷针
绕击
击距
雷云板
接闪率
lightning rod
shielding failure
striking distance
thundercloud simulative plate
flashover rate