期刊文献+

大规模风电接入下风电机组切机措施研究(英文) 被引量:24

Consideration of Wind Generator Tripping Under Large-scale Wind Power Integration
下载PDF
导出
摘要 风电接入比例增加,使得电力系统在某些严重故障下必须考虑风电(wind turbine generator,WTG)的切机措施。分析了风电机组和常规火电机组与系统电磁耦合关系的差异性;基于此,分析了风机和常规火电机组切机措施在保持系统稳定效果上的差异性。结果表明常规火电机组获得的加速能量大于风电机组(主要是双馈式风机),所以从保证切机后的功角稳定出发,应适当增加火电机组的切机量。对风电机组的频率和电压控制能力的分析表明:为保持故障后系统的正常运行,常规火电机组的切机比例也不宜过高;此外,风电机组出力的波动特性也将不可避免地影响切机措施的效果,为解决该问题,提出了考虑风电切机的切机措施的实时调整策略。 Increased penetration of wind generation has resulted in a need for wind turbine generator (WTG) tripping under some severe fault circumstances. The difference between electromagnetic coupling relationships of WTGs with system and that of conventional thermal units was analyzed. On this basis, the difference of tripping effects on system stability between WTGs and thermal units was studied. It shows that the accelerating energy gained by conventional unit is larger than that of WTG (mainly doubly fed induction generator (DFIG)) after the fault, so as far as the rotor angle stability after the generator tripping measure is concerned, it is better to trip the conventional unit rather than DFIG The frequency and voltage control capacities of DFIG were discussed. It is concluded that the tripping proportion of conventional units should not be too high due to the poor control capacities of DFIG. The impact of wind power fluctuation feature to the tripping measure was studied. The corresponding real-time adjustment means of WTG tripping measure was offered.
出处 《中国电机工程学报》 EI CSCD 北大核心 2011年第19期25-36,共12页 Proceedings of the CSEE
关键词 切机措施协调 风力发电机组 火电机组 系统稳定性 频率响应 风功率波动 generator tripping coordination wind turbine generator (WTG) thermal unit system stability frequency response wind power fluctuation
  • 相关文献

参考文献1

二级参考文献18

共引文献12

同被引文献308

引证文献24

二级引证文献558

相关作者

内容加载中请稍等...

相关机构

内容加载中请稍等...

相关主题

内容加载中请稍等...

浏览历史

内容加载中请稍等...
;
使用帮助 返回顶部