摘要
目的:选择13家使用中央空调系统的大型公共场所进行军团菌检测。方法:采集监测单位中央空调系统冷却塔水样进行军团菌分离、鉴定和计数。结果:13家单位共采集104件冷却塔水样,在5家场所(38.4%)的水样中检出嗜肺军团菌16株,检出数占样品总数的15.38%。结论:应加大监管力度,督促对中央空调进行清洗消毒。
Objective:Selecting 13 large-scale places using central air conditioning system to test their Legionella contamination.Methods: Collecting monitoring samples to carry on Legionella isolation,identification and counting.Results: In the 104 cooling tower water samples from 13 places,16 Legionella pneumophila strains(15.38%) in five places(38.4%) were detected.Conclusion: We should strengthen supervision and carry out the central air-conditioning units cleaning and disinfecting.