期刊文献+

交直流混联系统可靠性评估 被引量:19

Reliability estimation of AC/DC hybrid power system
下载PDF
导出
摘要 首先使用容量卷积公式计算出HVDC系统的容量-概率模型,然后对经典有功调整模型进行扩展,以模拟HVDC线路用于远距离输电和系统互联等场合。为了避免交直流系统交流潮流计算后出现平衡机出力越限问题,在有功调整模型中考虑了系统的有功损耗,并在纯交流系统可靠性评估无功/电压线性化校正模型的基础上,提出了计及HVDC线路影响的调整模型。最后对含HVDC线路的发输电系统进行了充裕度评估,研究了网损、电压及HVDC系统元件备用等因素对交直流系统可靠性指标的影响。 The capacity convolution method is used to derive the capacity-probability model of HVDC(High Voltage Direct Current) system and an improved active-power adjustment model is developed for the long-distance power transmission and interconnection of hybrid AC/DC power system,which considers the network active-power loss to avoid the output violation of generating units at the slack bus.Based on the linear reactive power and voltage adjustment model for AC system reliability estimation,an adjustment model is proposed to take the influence of HVDC into account.The adequacy estimation of power system with HVDC is investigated,including the effect of network loss and voltage,as well as the component backup of HVDC system on system reliability indices.
出处 《电力自动化设备》 EI CSCD 北大核心 2011年第7期10-16,共7页 Electric Power Automation Equipment
基金 国家自然科学基金资助项目(50777052) 教育部博士点基金资助项目(20100201110022)~~
关键词 交直流系统 可靠性 高压直流输电 容量卷积法 评估 AC/DC hybrid power system reliability HVDC power transmission capacity convolution method estimation
  • 相关文献

参考文献26

  • 1周浩,钟一俊.特高压交、直流输电的适用场合及其技术比较[J].电力自动化设备,2007,27(5):6-12. 被引量:58
  • 2BILLINTON R,AHLUWALIA D S. Incorporation of a DC link in a composite system adequacy assessment-DC system modelling [J]. lEE Proceedings-Generation,Transmission and Dislribution, 1992,139(3 ) :211-220.
  • 3KURUGANTY S. HVDC transmission system models for power system reliability evaluation[C]//IEEE Wescanex CommurLications, Power,and Computing. Manitoba,Canada:IEEE,1995:501-507.
  • 4KUMGANTY S. Effect of HVDC component enhancement on the overall system reliability perfommnce[J]. IEEE Transactions on Power Delivery, 1994,9( 1 ) :343-351.
  • 5BILLINTON R,ABORESHAID S,FOTUHI-FIRUZABAD M. Well -being analysis for HVDC transmission systems[J]. IEEE Transac- tions on Power Systems, 1997,12(2) :913-918.
  • 6BILLINTON R,ABORESHAID S,FOTUHI-FIRUZABAD M. Diag- nosing the health of bulk generation and HVDC transmission systems [J ]. IEEE Transactions on Power Systems, !997,12 (4) : 1740-1745.
  • 7LI Wenyuan. Probability distribution of HVDC capacity con- sidering repairable and aging failures[J]. IEEE Transactions on Power Delivery,2006,21 (1) :523-525.
  • 8LI Wenyuan,CHOUDHURY P,GILLESPIE D,et al. A risk eva- luation based approach to replacement strategy of aged HVDC components and its application at BCTC[J]. IEEE Transactions on Power Delivery, 2007,22 (3) : 1834-1840.
  • 9BILLINTON R,AHLUWALIA D S. Incorporation of a DC link in a composite system adequacy assessment-composite system analysis~J], lEE Proceedings-Generation,Transmission and Distri- bution, 1992,139 (3) : 221-225.
  • 10丁明.发输电系统可靠性分析软件综述[J].电网技术,2002,26(1):51-54. 被引量:26

二级参考文献126

共引文献246

同被引文献194

引证文献19

二级引证文献165

相关作者