摘要
采用确定与随机Petri网建立了Profibus-DP总线单主站系统报文传输延时的模型,并在TimeNet软件环境下对其进行了仿真分析,得出了报文传输延时与目标令牌循环时间的关系;并以STEP7软件为例,说明了在实际工程中如何根据Profibus-DP总线参数合理设定目标令牌循环时间、从而使监控系统获得最好的实时性的方法。仿真结果验证了该模型的正确性。
The paper used determinate and stochastic Petri net to establish a model of message transmission delay of Profibus-DP single master-station system and did simulation analysis in TimeNet software.It got relationship between message transmission delay and target-token cycle time and gave a method of setting target-token cycle time reasonably according to parameters of Profibus-DP in actual projects taking STEP7 software as an example,so as to make monitoring and control system get better real-time performance.The simulation result showed correctness of the model.
出处
《工矿自动化》
2011年第7期50-53,共4页
Journal Of Mine Automation
基金
天地(常州)自动化股份有限公司研发项目(10GY064)