介绍R32替代R410A在风冷冷热水机组上的应用研究,通过不同实验工况对比测试,结果表明:采用R32替代后,机组额定制冷量提高6%、额定制热量提高7%、制冷剂充注量减少30%。
Introduced R32 application reasearch on air-cooled water chiller heater unit instead of R410A.The performance experiment of various conditions were tested.The results showed that system refrigeration capacity risen by 6% or 7%,refrigerant charge decreased by 30%.
出处
《制冷空调与电力机械》
2011年第3期13-15,共3页
Refrigeration Air Conditioning & Electric Power Machinery
关键词
R32
风冷冷热水机组
实验
R32
air-cooled water chiller & heater unit
test