期刊文献+

矿用产品LonWorks总线接口保护技术

Protection Technology of LonWorks Bus Interface of Mine-used Products
下载PDF
导出
摘要 针对矿用产品LonWorks总线接口在实际应用中容易损坏的问题,分析了导致损毁的主要原因是收发信号不隔离、浪涌脉冲和长距离传输等因素,给出了3种由陶瓷气体放电管、自恢复保险丝、瞬态抑制二极管、静电放电保护器件组成的LonWorks总线接口保护电路。测试结果表明,该3种保护电路均满足有关标准的浪涌抗扰度测试要求,应用效果良好。 For the problem of frequent damage in application of LonWorks bus interface of mine-used products,main causes were analyzed including unisolating sending and receiving signals,electrical surge and long-distance transmission.Three protection circuits were gave which are composed of gas discharge tube,polymeric positive temperature coefficent,transient voltage suppressor and electro-static discharge protector.The test result showed that the three circuits can achieve corresponding standards about anti-interference testing of electrical surge and have good effect in use.
作者 孟庆勇
出处 《工矿自动化》 2011年第8期88-90,共3页 Journal Of Mine Automation
基金 "十一五"国家科技支撑计划项目(2009BAK54B04)
关键词 矿用产品 LONWORKS总线 接口保护 浪涌脉冲 陶瓷气体放电管 自恢复保险丝 瞬态抑制二极管 静电放电 mine-used product LonWorks bus interface protection electrical surge gas discharge tube polymeric positive temperature coefficent transient voltage suppressor electro-static discharge
  • 相关文献

参考文献3

二级参考文献5

  • 1陈显治.现代通讯技术[M].北京:电子工业出版社,2001:98-124.
  • 2李正军.现场总线及其应用技术[M].北京:机械工业出版社,2006.
  • 3戴恋.第三代LonWorks技术和产品.自动化博览,2002,(8).
  • 4刘蒙.Visual Basic中文版入门与提高实用教程[M].北京:中国铁道出版社,2003:5-50.
  • 5张玉春,杨成峰.现场总线集成技术[J].吉林电力,2008,36(1):1-4. 被引量:5