期刊文献+

动力分散系统中零压差点位置及水泵扬程的确定 被引量:11

Determination of zero-pressure point location and water pump head in distributed power systems
下载PDF
导出
摘要 运用水压图分析了零压差点位于不同位置时动力分散系统的水压分布。结果显示,零压差点应位于临界点与热(冷)源之间,才能消除调节阀能耗,从而使系统输配能耗最低;零压差点位于临界点与热(冷)源之间的不同位置时,水泵的配置方案不同,但各水泵的输出功率总和相等。 Using the pressure diagram analyses the pressure distribution of the distributed power system when the zero-pressure point is in different locations.The results show that the zero-pressure point should be at the location between the critical point and heat or cold source,which can cause the transmission energy consumption of the system to be lowest because of eliminating the energy consumption of the regulating valve,and that when the zero-pressure point is in different locations between the critical point and heat or cold source,disposition plans of water pumps are almost different,but total output powers of the pumps are the same.
作者 焦扬 符永正
机构地区 武汉科技大学
出处 《暖通空调》 北大核心 2011年第8期110-113,共4页 Heating Ventilating & Air Conditioning
关键词 动力分散系统 零压差点 临界点 水压图 水泵扬程 distributed power system zero-pressure point critical point pressure diagram water pump head
  • 相关文献

参考文献2

二级参考文献5

共引文献7

同被引文献40

引证文献11

二级引证文献22

相关作者