摘要
以瞬时无功功率理论为基础,对p-q检测方法在系统三相电压畸变、不对称状况下的检测结果进行理论分析。给出了电流检测的误差来源;同时提出了系统电压基波正、负序分离新方法,对传统p-q检测方法进行改进,消除了电压畸变、不对称电流检测误差。
The theoretical analysis of the test results is given based on p-q detection method in the system three-phase voltage distortion and a- symmetry. System voltage fundamental positive and negative sequence separation module is proposed based on traditional p-q detection method, which have solved the voltage distortion, asymmetry detection error, that is to say, voltage distortion and asymmetrical would not affect the fundamental positive and negative sequence current detection.
出处
《世界科技研究与发展》
CSCD
2011年第4期636-640,共5页
World Sci-Tech R&D
关键词
谐波检测
瞬时无功
电压基波正序分离
harmonic detection
instantaneous reactive power
fundamental frequency positive-sequence separation of voltage