期刊文献+

多功能热泵空调与热水负荷调节的理论分析与试验研究 被引量:2

The Theoretical Analysis and Experimental Study of Multi-funtion Heat Pump in Regulating Load of Hot Water and Air-conditioning
下载PDF
导出
摘要 为了解决多功能热泵空调兼制热水工况时热泵的能量输出与热水负荷和空调负荷之间的平衡问题,就必须根据空调或热水的负荷的变化对热水换热量和空调换热量进行能量调节。首先,对现有的几种能量调节方式进行了分析,针对各自的优缺点,提出了一种新的变流量调节方式,并进行了理论可行性分析;然后进行试验研究,实验结果表明,增加热水换热器循环水流量能加大热水换热量、减少空调换热量;降低热水换热器循环水流量能减少热水换热量、加大空调换热量。因此,可采用以满足空调负荷为控制目标,通过变热水换热器循环水流量的方式对热水和空调的热量分配进行动态调节。 In order to solve the load balance of hot water and air-conditioning in multi-function heat pump under air-conditioning and water heating mode,it is necessary to regulate the energy exchange between hot water heat exchanger and air-conditioning heat exchanger according to the load changing of air-conditioning or hot water.At first,several kinds of current adjusting methods of energy is analyzed,and a new variable flow regulating mode is proposed based on the advantages and disadvantages of current methods.The theoretical feasibility is analyzed.Then,the performance of new regulating mode is experimentally investigated.The results show that increase in water flow of hot water heat exchanger can enhance the energy exchange of hot water heat exchanger and reduce the energy exchange of air-conditioning heat exchanger,and vice versa.Therefore,the heat distribution between hot water heat exchanger and air-conditioning heat exchanger can be dynamically adjusted by varying the water flow rate of hot water heat exchanger when the air-conditioning load is satisfied as control target.
作者 江乐新 钟杰
机构地区 中南大学
出处 《制冷学报》 CAS CSCD 北大核心 2011年第4期39-42,共4页 Journal of Refrigeration
关键词 热工学 多功能热泵 空调兼制热水模式 负荷调节 变流量 Pyrology Multi-function heat pump Air-conditioning and water heating model Load regulation Variable flow
  • 相关文献

参考文献4

二级参考文献16

  • 1季杰 等.家用空调和热水器一体化装置[P].00 2 40603.9.2001-07-06.
  • 2[1]Domijan A,Embriz-Santander E.Measurement of electrical power inputs to variable-speed motors and their solid-state power converters.ASHRAE Trans.,1993,99(1):241~258
  • 3[2]Zubair S M,Habel V.Compressor capacity modulation schemes.Heating, Piping,Air Conditioning,1989 (1):135~143
  • 4[3]Tassou S A,Qureshi T Q.Comparative performance evaluation of positive displaycement compressors in variable-speed refrigeration applications.Int.J.Refrig., 1998,212(1):29~41
  • 5[4]Cooper W D.The use of mixed refrigerants in air-to-air heat pumps.ASHRAE Trans.,1992,part 2:320~325
  • 6[5]VaKi H B.New concept in capacity modulation using non-azeotropic mixtures.General Electric Reports,1983,83:212
  • 7Gorzelnik E F. Heat water with your air-conditioner. Electrical World. 1977.188( 11 ).
  • 8Rousseau P G, Greyvenstein G P. Enheancing the impact of heat pump water heaters in the South African commercial sector. Energy, 2000,25:51 - 70.
  • 9Heap R D. Heat Pumps. ,Second Edition. London: E & F NSpon, 1983.
  • 10Vince C Mei, Ronald E, et al. Experimental study of an R-407C heat pump water heater. ASHRAE Trans, 2001,A.