期刊文献+

倒挂式电缆终端渗水的原因分析与防治方案 被引量:1

The Causes Analysis and Prevention of Water Penetration of Underslung Cable Terminal Set
下载PDF
导出
摘要 地下变电站内电缆终端渗水是目前电缆线路运行中比较严重的缺陷之一,而且近几年问题日趋严重。分析了电缆终端渗水的原因,讨论了上海市电力公司检修公司多年来对电缆终端渗水处理的常用方法及其利弊,提出了防治的综合封堵方案,并详细介绍了该方案的施工步骤。在上海地区电缆线路的运行实践,证明了该方案的有效性。 The water penetration of cable terminal set in the underground substation is one of the serious defect in the cable operation presently, and recently becomes serious gradually. The causes of the water penetration are analyzed. The ordinary methods used in Maintenance Company, SMEPC for many years are discussed, together with their advantages and disadvantages. The comprehensive sealing scheme to prevent the penetra- tion is presented, as well as its construction procedure in detail. Its application in cable lines in Shanghai has proven the effectiveness of this scheme.
作者 王健敏 金辉
出处 《供用电》 2011年第4期72-75,共4页 Distribution & Utilization
关键词 地下变电站 电缆终端渗水 综合封堵 underground substation water penetration of cable terminal set comprehensive sealing
  • 相关文献

参考文献6

  • 1陈蘅.电力设备故障红外诊断[M].北京:水利电力出版社,1999.
  • 2福岛肇日著,王旭译.电磁悬念关于电和磁的推理故事[M].北京:科学出版社,2006.
  • 3戴道生 钱昆明.铁磁学[M].北京:科学出版社,1987..
  • 4严济慈.电磁学[M].北京:清华大学出版社,1978.
  • 5国家电网公司.Q/GDW168-2008输变电设备状态检修试验规程[S].北京:中国电力出版社,2008.
  • 6国家电网公司.Q/GDW173-2008架空线路状态评价导则[s].北京:中国电力出版社,2008.