西北高土壤电阻率地区线路接地电阻的测量方法 被引量:2

Research on Tower Grounding Resistance Measurement in Northwest Region with High Soil Resistivity
原文传递
导出
摘要 高土壤电阻率地区杆塔接地电阻存在无法测出的问题。通过理论计算认为,高土壤电阻率导致辅助接地探测棒接地电阻过大,从而导致接地电阻仪失灵。提出的措施为:增加辅助接地探测棒的长度和直径、提高土壤含水量、使用食盐做降阻剂。现场试验的结果证明了该方法的正确性和合理性。 The grounding resistance measurement instrument fails in high soil resistivity because the grounding resistance is too high of auxiliary grounding detection rod from the theoretical analysis. In order to improve the sensitivity of measurement instrument, it is proposed to increase the length and diameter of auxiliary grounding detection rod, enhance the water content of soil and apply salt for decreasing resistance. The correctness and reasonability of the proposed method are validated by field experiment.
出处 《电力建设》 2011年第9期33-36,共4页 Electric Power Construction
关键词 高土壤电阻率 接地电阻 测量方法 ZC-8 接地型式 辅助接地探测棒 high soil resistivity grounding resistance measurement ZC -8 grounding modes auxiliary grounding detection rod
  • 相关文献

参考文献9

二级参考文献28

共引文献207

同被引文献55

  • 1张秀丽,马茜,王应高,黄治娟,赵蓓蕾.钢接地体在降阻剂中腐蚀速率测量方法的研究[J].腐蚀科学与防护技术,2015,27(1):69-72. 被引量:5
  • 2郑瑞臣,李景禄.关于接地降阻材料的应用研究[J].电瓷避雷器,2005(5):43-46. 被引量:14
  • 3GB 50150-2006,《电气装置安装工程电气设备交接试验标准》[S].
  • 4《建筑物防雷设计规范》GB50057-2010[S].
  • 5GB26861-2011《电力安全工作规程(高压试验室部分)》[s].
  • 6DIMT1082-2008《高压实验室技术条件》[S].
  • 7王森,李志忠,徐晓晴,等.大型接地装置的性能测试与综合评价[J].电网技术,2011,12:28-32.
  • 8GB50065-2011《交流电气装置的接地设计规范》[s].
  • 9谈莹,周惠黎,程晔新.高压试验厅的接地设计[J].低压电器,2007(24):39-43. 被引量:8
  • 10Robert M, Marek I., Radoslaw N. Influence of climatic condi tions in China on reliability of power earthing system[C]. 2010 Asia-Pacific International Symposium on Electromagnetic ComL patibility, Beiiing, 2010,1542 1546.

引证文献2

二级引证文献5

相关作者

内容加载中请稍等...

相关机构

内容加载中请稍等...

相关主题

内容加载中请稍等...

浏览历史

内容加载中请稍等...
;
使用帮助 返回顶部