下送风通信机柜发热量改变对其出风温度的影响 被引量:1

Influence of Heat Change on Outlet Temperature in Communication Cabinet with Downside Air Supply
下载PDF
导出
摘要 根据空调精确下送风的原理,建立了精确下送风单机柜实验台,并通过3个工况的实验分析了机柜发热量改变对其出风温度的影响,实验结果表明:减小机柜的发热量,则机柜的出风温度随之减小,当标准机柜发热量从4995W减小到3004W时,机柜出风侧的最高温度由34.8℃减小至26.7℃,通信设备出风口的温度由39.5℃减小至31.4℃。因此,安装通信设备时,应根据最大出风温度限值要求确定标准机柜的最佳装机容量。 According to the principle of accurate downside air supply,an experimental platform of single communication cabinet was established,and under three experimental conditions the influence of heat change on outlet temperature in cabinet was analyzed.The results showed that: The outlet temperature decreased as the heat decreased in the cabinet.When the heat of the standard cabinet decreased from 4995W to 3004W,the maximal outlet temperature of the cabinet decreased from 34.8℃to 26.7℃,and the maximal outlet temperature of the communication device decreased from 39.5℃ to 31.4℃.Therefore,the best installed capacity of the standard cabinet based on the limits of maximal outlet temperature in communication device installation.
出处 《洁净与空调技术》 2011年第3期17-20,共4页 Contamination Control & Air-Conditioning Technology
关键词 精确下送风 机柜 发热量 出风温度 Accurate downside air supply Communication cabinet Heat Outlet temperature
  • 相关文献

参考文献3

二级参考文献5

  • 1孙研.通信机房节能综合解决方案[J].电信工程技术与标准化,2006,19(6):2-7. 被引量:18
  • 2劳逸民.IDC机房的空气调节系统设计[J].智能建筑电气技术,2007,1(1):61-65. 被引量:2
  • 3Jinkyun Cho,Taesnb Lim,Byungseon Scan Kim.Measurements and predictions of the air distribution systems in high compute density(Internet)data centers[J].Energy and Buildings,2009,41:1107-1115.
  • 4J K Cho,B S Kim,C S Jeong,The planning and design of the optimal cooling system for IT environments in data centers[J].Journal qf the Architectural Institute of Korea,2008,24(12):313-320.
  • 5中国电信数据中心机房电源、空调环境没汁规范(暂行)[S].北京:中国电信集团公司,2005.

共引文献33

同被引文献4

引证文献1

二级引证文献2

相关作者

内容加载中请稍等...

相关机构

内容加载中请稍等...

相关主题

内容加载中请稍等...

浏览历史

内容加载中请稍等...
;
使用帮助 返回顶部