期刊文献+

Experimental Performance of Moderate and High Temperature Heat Pump Charged with Refrigerant Mixture BY-3 被引量:2

Experimental Performance of Moderate and High Temperature Heat Pump Charged with Refrigerant Mixture BY-3
下载PDF
导出
摘要 Theoretical and experimental analysis of a new refrigerant mixture BY-3 was conducted based on a single-stage vapor compression refrigeration system. The water-water heat pump system used BY-3 to produce hot water when the low temperature was 20 ℃. The following results were obtained: the highest temperature at the condenser outlet reached about 85 ℃; when the difference between the water temperatures at the condenser outlet and the evaporator inlet was less than 40 ℃, the coefficient of performance (COP) was larger than 4; when the difference reached 55 ℃, the COP still kept 3; the discharge temperature of BY-3 was lower than 100 ℃, and the refrigerant vapor pressure kept lower than 1.8 MPa. When the water temperature at the condenser outlet reached over 85 ℃, nearly a 5 ℃ superheating temperature was maintained. Theoretical and experimental analysis of a new refrigerant mixture BY-3 was conducted based on a singlestage vapor compression refrigeration system. The water-water heat pump system used BY-3 to produce hot water when the low temperature was 20 ℃. The following results were obtained: the highest temperature at the condenser outlet reached about 85 ℃; when the difference between the water temperatures at the condenser outlet and the evaporator inlet was less than 40 ℃, the coefficient of performance (COP) was larger than 4; when the difference reached 55 ℃, the COP still kept 3; the discharge temperature of BY-3 was lower than 100 ℃, and the refrigerant vapor pressure kept lower than 1.8 MPa. When the water temperature at the condenser outlet reached over 85 ℃, nearly a 5 ℃ superheating temperature was maintained.
出处 《Transactions of Tianjin University》 EI CAS 2011年第5期386-390,共5页 天津大学学报(英文版)
基金 Supported by Major State Basic Research Development Program of China ("973" Program, No. 2009CB219907) the Program for Changjiang Scholars and Innovative Research Team in University (No. IRT0936)
关键词 混合制冷剂 实验成绩 高温热泵 压缩式制冷系统 出口水温 最高温度 冷凝器 实验分析 moderate and high temperature heat pump refrigerant mixture single-stage compression heat pump system coefficient of performance
  • 相关文献

参考文献16

  • 1Han X H, Wang Q, Zhu Z Wet al. Cycle performance study on R32/R125/R161 as an alternative refrigerant to R407C[J]. Applied Thermal Engineering, 2007, 27 (14/15) : 2559-2565.
  • 2Park K J, Jung D. Performance of heat pumps charged with R170/R290 mixture[J]. Applied Energy, 2009, 86(12): 2598-2603.
  • 3Devotta S, Waghmare A V, Sawant N Net al. Alternatives to HCFC-22 for air conditioners [J]. Applied Thermal En- gineering, 2001, 21 (6): 703-715.
  • 4Spatz Mark W, Motta Samuel F Yana. An evaluation of options for replacing HCFC-22 in medium temperature re- frigeration systems [J]. International Journal of Refrigera- tion, 2004, 27 (5) : 475-483.
  • 5Wu J T, Chu Y J, Hu Jet al. Performance of mixture re- frigerant R152aYR125JR32 in domestic air-conditioner[J]. International Journal of Refrigeration, 2009, 32 (5) : 1049- 1057.
  • 6Mohanraj M, Jayaraj S, Muraleedharan C. Environment friendly alternatives to halogenated refrigerants--A re- view [J]. International Journal of Greenhouse Gas Con- trol, 2009, 3 (1) : 108-119.
  • 7Park K J, Shim Y B, Jung D. A 'drop-in' refrigerant R431A for replacing HCFC22 in residential air-conditioners and heat pumps [J]. Energy Conversion and Management, 2009, 50(7): 1671-1675.
  • 8Mani K, Selladurai V. Experimental analysis of a new refrigerant mixture as drop-in replacement for CFC 12 and HFC 134a [J]. International Journal of Thermal Sciences, 2008, 47 (11) : 1490-1495.
  • 9Chaturvedi S K, Abdel-Salam T M, Sreedharan S S et al. Two-stage direct expansion solar-assisted heat pump for high temperature applications [J]. Applied Thermal Engi- neering, 2009, 29 (10): 2093-2099.
  • 10Kim M, Baik Y J, Park S R et al. Design of a high tempera- ture production heat pump system using geothermal water at moderate temperature[J]. Current Applied Physics, 2010, 10(2): 117-122.