期刊文献+

从空调定压方式浅析地埋换热系统超压泄露问题

ANALYSIS ON OVER-PRESSURE LEAKAGE OF UNDERGROUND HEAT EXCHANGE SYSTEM BY AIR-CONDITIONER PRESSURIZATION PATTERN
下载PDF
导出
摘要 针对地源热泵系统设计不当和定压方式选择不当造成的超压泄漏问题,设置地源换热器定压方式为开式膨胀水箱定压,即静水柱定压。当冷热转换阀门出现泄漏,可通过开式膨胀水箱的排泄溢流作用保护地源换热器,从而避免超压泄漏事故的发生。因其压力恒定,自动补水,同时有超压排泄溢流的优点,安全可靠,尤其适用于高大建筑的地源换热器设计施工中。 Aim at over-pressure leakage in poor design and improper selection for the constant pressure mode in ground source heat pump system,set pressurization mode for ground-coupled heat exchanger to be open expansion water tank pressurization,that is,static water pressurization.When hot and cold conversion valves leak,ground source heat exchanger is protected by overflow discharge of open expansion water tank so as to avoid overpressure leak accident.Because pressure is constant,automatic fill water,and over-pressure drainage overflow,it is safe and reliable,especially for ground source heat exchanger in design and construction of tall building.
作者 郝君
出处 《山东农业大学学报(自然科学版)》 CSCD 北大核心 2011年第4期539-542,共4页 Journal of Shandong Agricultural University:Natural Science Edition
关键词 超压泄露 空调定压方式 地埋换热系统 over-pressure leakage air-conditioner pressurization pattern underground heat exchange system
  • 相关文献

参考文献6

  • 1地源热泵系统地埋管换热器施工技术规程GB50366-2005.
  • 2丁勇 李百战 卢军 等.地源热泵系统地下埋管换热器设计(1)[J].HEATING VENTILATING&AIR CONDITIONING,2005,.
  • 3庄迎春,孙友宏.地源热泵地下直埋式换热器的施工[J].探矿工程,2002(3):10-11. 被引量:11
  • 4Kevin Rafferty , P. E. An Information Survival Kit for the Prospective Geothermal Heat Pump Ownetr[ Z] . U. S. A : Geo - heat Center. 1997.
  • 5梁军,戴传山,张启.中低温地热井下换热供热实验研究[J].太阳能学报,1997,18(4):437-439. 被引量:3
  • 6EPA. Geothermal Heat Pumps [ Z] . U. S. A : ClimateChangeTechnologies ,2000.