一种新型并网逆变器电流控制策略的研究 被引量:21

Research on the new current control strategy based on the grid-connected inverter
下载PDF
导出
摘要 针对并网逆变器采用传统滞环空间矢量控制时存在的交流侧电流谐波总畸变率(Total Harmonic Distortion,THD)相对较大的缺点,提出分段控制的改进思想,即通过对交流侧误差电流矢量模值大小判断后,交替使用滞环控制与滞环空间矢量控制。给出电压合成矢量和交流误差电流矢量的空间划分方法,以及分段控制下开关状态的选择原则。利用Matlab/Simulink对改进前后的控制方案进行对比,结果表明改进后的控制策略不仅可以实现单位功率因数并网,还可以达到在减少开关损耗的同时,有效地降低交流侧电流谐波总畸变率(THD)。 The improved segment control strategy is introduced aiming at the disadvantage of the larger AC current total harmonic distortion (referred to as THD) caused by the traditional space vector hysteresis control in the grid-connected inverter. The improved segment control strategy alternates hysteresis control and space vector hysteresis control strategies through the judgment of the AC error current vector modulus. The space region division of the voltage synthetic vector synthetic and the AC error current vector are given, and the selection principle of the switch state under segment control strategy is provided. Finally, the simulation model is established under Matlab/Simulink by comparing the traditional and the improved control strategies, the simulation results further demonstrate the improved control scheme not only can achieve the unity power factor, but also can reduce the AC current total harmonic distortion (THD) and the switching losses effectively.
出处 《电力系统保护与控制》 EI CSCD 北大核心 2011年第20期137-140,共4页 Power System Protection and Control
关键词 逆变器 并网 滞环空间矢量控制 滞环控制 分段控制 inverter grid-connected space vector hysteresis control hysteresis control segment control
  • 相关文献

参考文献4

二级参考文献35

  • 1姜俊峰,刘会金,陈允平,孙建军.有源滤波器的电压空间矢量双滞环电流控制新方法[J].中国电机工程学报,2004,24(10):82-86. 被引量:108
  • 2付青,罗安,王莉娜.基于自适应智能控制的混合有源电力滤波器复合控制[J].中国电机工程学报,2005,25(14):46-51. 被引量:29
  • 3刘飞,邹云屏,李辉.基于重复控制的电压源型逆变器输出电流波形控制方法[J].中国电机工程学报,2005,25(19):58-63. 被引量:54
  • 4EI-Habrouk M, Darwish M K, Mehta P. Active Power Filter: a Review[J]. IEE Proceeding-Electric Power Applications, 2000, 147(5): 403-413.
  • 5Kwon B H, KimTW, Youm J H. ANovel SVM-based Hysteresis Current Controller[J]. IEEE Trans on Power Electronics, 1998, 13(2): 297-307.
  • 6Marei M I, El-Saadany E F, Salama M M A. A New Contribution Into Performance of Active Power Filter Utilizing SVM Based HCC Technique[J]; Power Engineering Society Summer Meeting, 2002, 2(2): 1022-1026.
  • 7Ha betler T G.A Space Vector Based Rectifier Regulator for AC/DC/AC Converters[J].IEEE Trans.Power Elec,1993,8(1):58-66.
  • 8Blasko.V.Analysis of a Hybrid PWM Based on Modified Space-Vector and Triangle Comparison Methods.IEEE Trans on IA,1997,33(3):756-764.
  • 9Yokoyama T, Kawamura A. Disturbance Observer Based Fully Digital Controlled PWM Inverter for CVCF Operation [J]. IEEE Trans on Pow Electr, 1994,9(5):473-480.
  • 10Miret J, de Vicuxia L G, Castilla M. A Simple Sliding Mode Control of an Active Power Filter[A]. Power Electronics Specialists Conference. 2004. 1052-1056.

共引文献57

同被引文献184

引证文献21

二级引证文献145

相关作者

内容加载中请稍等...

相关机构

内容加载中请稍等...

相关主题

内容加载中请稍等...

浏览历史

内容加载中请稍等...
;
使用帮助 返回顶部