期刊文献+

1000MW机组循环水系统特性差异比较与试验分析 被引量:1

Comparison of Characteristic Differences and Test Analysis for 1 000 MW Unit Circulating Water System
下载PDF
导出
摘要 同一型号的超超临界1 000 MW机组分别采用海水开式循环和冷却塔闭式循环这两种不同的循环水冷却方式后,不仅对循环水泵选型提出了不同的要求,而且还引起了凝汽器类型和冷却面积、设计压力等方面的优化设计差异。通过对2台1 000 MW机组采用不同方式的循环水系统设计参数和试验结果分析,对循环水泵、凝汽器等冷端设备的性能参数进行差异比较,进而对整机运行性能的影响程度作出评估,并提出冷端设备优化调整方面的建议。 The adoption of the circulating water cooling methods of the seawater open circulation and cooling tower closed circulation for the ultra-supercritical 1 000 MW units of the same model not only leads to the different requirements for circuiting water pump selection,but also results in the optimization design differences in terms of condenser type,cooling area,design pressure etc.Through the analysis of the design parameters and test results of the different circulating water systems adopted for two 1 000 MW units,this paper compares the performance parameter differences between circulating water pump,condenser and other cold-end equipments,evaluates the influence on the operation performance of the whole unit and offers the proposals for the optimization of cold-end equipments.
出处 《浙江电力》 2011年第9期30-33,46,共5页 Zhejiang Electric Power
关键词 1000MW机组 循环水系统 差异 比较 分析 1 000 MW unit circulating water system differences comparison analysis
  • 相关文献

参考文献2

二级参考文献6

  • 1梁磊,周国定,倪鹏,张登云,孙志林,孙军,王义好.铜陵电厂凝汽器黄铜管换不锈钢管[J].汽轮机技术,2004,46(4):305-307. 被引量:7
  • 2N1000-26.25/600/600型1000MW超超临界中间再热凝汽式汽轮机热力特性数据[R].上海:上海电气电站设备有限公司上海汽轮机厂.
  • 3中国国家质量监督检验检疫总局.GB/T8117.2-2008汽轮机热力性能验收试验规程[S].北京:中国标准出版社.2008.
  • 4.湖北省荆门热电厂2×600 MW超临界汽轮机设备采购合同(附件)[R].北京,2004年1月..
  • 5Standards for Steam Surface Condensers Copyright January,1995 by Heat Exchange Institute (Ninth Edition).
  • 6Standards for Steam Surface Condensers Copyright January,1984 by Heat Exchange Institute.

共引文献11

同被引文献3

引证文献1

相关作者

内容加载中请稍等...

相关机构

内容加载中请稍等...

相关主题

内容加载中请稍等...

浏览历史

内容加载中请稍等...
;
使用帮助 返回顶部