摘要 针对220 kV系统不配置单独的远跳装置,发生死区故障时无法利用远跳装置跳对侧开关的问题,以某变电站的220 kV系统为例,详细介绍了利用现有保护装置远跳对侧开关、快速切除故障的设计方案。实际应用表明,该220 kV系统发生死区故障时远跳对侧的相关二次回路运行状况良好,从而验证了该设计方案的正确性。 In view of problem of no remote tripper to trip opposite switch when 220 kV system appears dead-zone fault,the paper detailedly introduced design scheme of using current protection devices to trip opposite switch to clear fault quickly by taking 220 kV system of one substation as example.The actual application showed that concerned secondary circuit of remote tripping opposite switch runs well when the 220 kV system appears dead-zone fault,which validates correctness of the design scheme.
出处 《工矿自动化》 2011年第10期79-81,共3页 Journal Of Mine Automation
关键词 220KV线路 死区故障 远跳对侧 断路器 电流互感器 220 kV line dead-zone fault remote tripping opposite switch breaker current transformer
  • 相关文献

参考文献6

  • 1赵佰成,徐炜彬,曲绍杰.220kV典型保护死区问题的探讨[J].电力系统保护与控制,2010,38(13):130-132. 被引量:27
  • 2李季,陶丽莉,屈自强,孙磊.变电站继电保护死区的改进措施[J].电工技术,2009(8):8-9. 被引量:4
  • 3俞胜,马继政,钱美芳,高华英.一种线路死区的保护方式[J].电力系统保护与控制,2008,36(23):113-115. 被引量:8
  • 4GB/T14285-2006.中华人民共和国国家质量监督检验检疫总局.继电保护和安全自动装置技术规程[S].北京:中国标准出版社,2006:12-25.
  • 5国家电网公司.Q/GDWl61--2007线路保护及辅助装置标准化设计规范[S/OL].(2009-02-17)[2011-05-31].http://www.jdzj.com/diangong/article/2009-2-17/5396-1.htm.
  • 6国家电网公司.Q/GDW175-2008变压器、高压并联电抗器和母线保护及辅助装置标准化设计规范[S].北京:中国电力出版社,2008.