摘要
针对35 kV架空线路因雷击造成的复合绝缘子损坏和导线断线等问题,进行了引弧并联间隙的研究,提出了引弧并联间隙的尺寸要求。大量的冲击和工频特性试验表明,引弧并联间隙能够有效保护复合绝缘子串和导线免受工频续流电弧的蚀烧;计算了线路的雷击跳闸率,建议在原线路绝缘的基础上适当提高线路绝缘距离后,再加装引弧并联间隙。
For solving the problems of the damages of both composite insulator string and conductors which caused by lightning stroke in 35 kV overhead transmission lines, arc ignition parallel gap is studied, and the dimension demand of arc ignition parallel gap is proposed, the results of lots of lighting impulse and power frequency arcing tests show that arc ignition parallel gao can effectively make composite insulators and conductors exclusive from ablation of power frequency arc caused by lightning stroke; By calculating the trip-out rate of transmission line, it is suggested to increase line insulation distance on the basis of the original line insulation before retrofitting arc ignition parallel gap.
出处
《电瓷避雷器》
CAS
北大核心
2011年第5期16-20,共5页
Insulators and Surge Arresters
关键词
35KV架空线路
复合绝缘子串
引弧并联间隙
防雷保护
跳闸率
35 kV overhead transmission lines
composite insulator string
arc ignition parallel gap
lightning protection
trip-out rate