期刊文献+

电压间谐波分量对荧光灯闪变效应的研究 被引量:4

An Investigation on the Flicker of Fluorescent Lamp Caused by Interharmonic Voltages
下载PDF
导出
摘要 运用调制理论,对自激式电子镇流器荧光灯在间谐波导致的闪变电压下的功率波动进行理论分析,得到了在电源电压中含间谐波分量时荧光灯的功率响应,建立了荧光灯瞬时功率波动特征与间谐波特征之间的关系曲线。利用Matlab/Simulink软件对该研究对象进行的仿真和实验研究,验证了理论分析结果的正确性。理论分析和实验结果均表明电源电压中的间谐波分量可能导致荧光灯闪变,且闪变频率与间谐波造成的电压波动频率相同。荧光灯瞬时功率波动特征与间谐波特征之间关系的建立,有助于进一步对荧光灯在间谐波电压条件下的闪变效应进行评价方法研究,及其间谐波闪变限制标准的制定。 Based on modulation theorem,theoretical study was carried out to obtain the input power fluctuation of the fluorescent lamp(FL) with self-oscillating electronic ballast supplied by voltages including interharmonics.And the relationship between characteristics of FL's instantaneous power fluctuation and interharmonics is established.The simulation and experimental results confirm that the proposed methods are valid.Both theoretical and experimental results show that the interharmonic component included in supply voltage indeed leads flicker of FLs and the flicker frequency equals the voltage fluctuation frequency caused by interharmonics.The established relationship between FL's instantaneous power fluctuation and interharmonics is helpful to further research on the evaluating flicker effect of interharmonics on FLs and framing the flicker limit standard of interharmonics.
出处 《电工技术学报》 EI CSCD 北大核心 2011年第10期16-22,38,共8页 Transactions of China Electrotechnical Society
基金 国家自然科学基金资助项目(51077138)
关键词 间谐波 闪变 功率波动 荧光灯 电子镇流器 Interharmonic flicker power fluctuation fluorescent lamp electronic ballast
  • 相关文献

参考文献17

  • 1中华人民共和国国家标准.电能质量电压波动和闪变[S].标准出版社.2008.
  • 2IEC 61000-4-15, Testing and measurement techniques: flickermeter-functional and design specifications[S].
  • 3Yacamini R. Power system harmonics-part 4 inter- harmonics[J]. Power Engineering Journal, 1996, 10(4): 185-193.
  • 4Tayjasanant T, Xu W. A case study of flicker/ interharmonic problem caused by a variable frequency drive[C]. 1 lth International Conference on Harmonics and Quality of Power, 2004:72-76.
  • 5Li C, Xu W, concepts and Tayjasanant techniques T. Interharmonics: basic for their detection and measurement[J]. Electric Power Systems Research 2003, 66(1): 39-48.
  • 6Halpin S M, Bergeron R, Blooming T M, et al. Voltage and lamp flicker issues: should the IEEE adopt the IEC approach[J]. IEEE Transactions on Power Delivery, 2003, 18(3): 1088-1097.
  • 7Tayjasanant T, Wang W, Li C, et al. Interharmonic- flicker curves[J]. IEEE Transactions on Power Delivery, 2005, 20(2): 1017-1024.
  • 8Yong J, Tayjasanant T, Xu W. Characterizing voltage fluctuations caused by a pair of interharmonics[J]. IEEE Transactions on Power Delivery, 2008, 23(1): 319-327.
  • 9Gallo D, Landi C, Langella R, et al. IEC flickermeter response to interharmonic pollution[C]. 11th Interna- tional Conference on Harmonics and Quality of Power, 2004: 489:494.
  • 10Gluskin E, Topalis F V, Kateri I. The instantaneous light-intensity function of a fluorescent lamp[J]. Physics Letters A, 2006, 353: 355-363.

二级参考文献24

  • 1张晶.多谐波源系统谐波叠加方法的研究[J].电网技术,1995,19(3):23-27. 被引量:48
  • 2ASPLUND G, ERIKSSON K,SVENSSON K. HVDC LightDC Transmission Based on Voltage Source Converters. ABB Review,1998, 1(1): 4-9.
  • 3ZHANG Guibin, XU Zheng. Steady-state Model for VSC Based HVDC and Its Controller Design. In: Proceedings of IEEE PES Transmission and Distribution Conference, Vol 3.Columbus (OH, USA): 2001. 1085-1090.
  • 4CAMACHO S M,COLLINS E R.A harmonic model of a 2-pulse DC motor drive operating in the continuous current mode[A ].Proceedings of the 1994 IEEE 10-13[C ].1994.40-44.
  • 5CARPINELLI G,IACOVONE F,RUSSO A.Analytical modeling of harmonic analysis of line current of VSI-FED drives[ J ].IEEE Trans.on Power Delivery,2004,19 (3):1212-1222.
  • 6CAVALLINI A,MONTANARI G C,CACCIARI M.Stochastic evaluation of harmonics at network buses[J ].IEEE Trans.on Power Delivery,1995,10(3):1606-1613.
  • 7CAVALLINI A,MONTANARI G C.A deterministic/stochastic framework for power system harmonics modeling[J].IEEE Trans.on Power Systems,1997,12(1):407-415.
  • 8EMANUEL A E,ORR J A,CYGANSKI D,et al.A survey of harmonic voltages and currents at the customer's bus[J].IEEE Trans.on Power Delivery,1993,8 (1):411-421.
  • 9KAPRIELIAN S R,EMANUEL A E,DWYER R V.Predicting voltage distortion in a system with multiple random harmonics sources[J ].IEEE Trans.on Power Delivery,1994,9(3):1632-1638.
  • 10BAGHZOUA Y,BURCH R F,CAPASSO A.Time-varying harmonics:part Ⅱ-harmonic summation and propagation[J ].IEEE Trans.on Power Systems,2002,17 (1):279-285.

共引文献47

同被引文献54

引证文献4

二级引证文献34

相关作者

内容加载中请稍等...

相关机构

内容加载中请稍等...

相关主题

内容加载中请稍等...

浏览历史

内容加载中请稍等...
;
使用帮助 返回顶部