摘要
在孤立电网中快速、准确地选出临界机群,加强临界机群的调频能力,能够提高孤网的稳定性。从发电机原始转子运动方程出发,研究了不平衡功率积分和转子角动量对时间积分的物理意义;分析了它们同惯性时间常数的关系,提出了根据发电机角动量增量选择临界机群的性能指标。将角动量选择临界机群与暂态稳定计算中的分段计算法选择临界机群相比较,体现了角动量选择临界机群的优越性。通过优化调速器参数加强临界机群的一次调频能力,从而提高孤立电力系统频率稳定性。并以孤网四机系统为例,用仿真实验验证了方法的可行性和优越性。
Choosing the critical generators quickly and accurately and strengthening the frequency regulation ability can improve the system stability of isolated grid. Based on the generator rotor motion equation, this paper studies the physical significance of rotor imbalance of power and angular momentum points to time integral. Their relationship with the time constant of inertia is analyzed and the performance index of choosing critical units according to incremental angular momentum of the generator is proposed. Compared with the angular momentum index and transient stability calculation of subsection calculation method, its superiority is reflected. By optimizing the governor parameters of critical units, the regulation ability of a critical frequency is strengthened, thus the system frequency stability is improved. Taking the four-machine system in the isolated grid as an example, simulation results verify the feasibility and superiority of the method.
出处
《电力系统保护与控制》
EI
CSCD
北大核心
2011年第23期39-43,48,共6页
Power System Protection and Control
基金
'十一五'国家科技支撑计划项目(2008BAA13B01)
国家自然科学基金资助项目(50877050)~~
关键词
一次调频
角动量
惯性时间常数
调速器
primary frequency regulation
angular momentum
time constant inertia
governor