摘要 对500 kV的全尺寸绝缘子进行覆冰闪络试验,得到了在不同覆冰条件下的闪络电压值,据此设计不同覆冰条件下具有95%耐受概率所需的线路绝缘子最优串长。最后提出改变绝缘子配置和使用防冰涂料等综合方式来提高绝缘子防冰效果的措施。 Icing flashover test is conducted on 500 kV full-length insulators and magnitudes of flashover voltage in different icing conditions are concluded. According to the test, the length of icing insulator strings with 95% probability of tolerance voltage in different icing thickness is designed. Furthermore, the paper put forward comprehensive methods by changing configuration and painting anti-icing coating to improve the anti-icing effect of insulators.
出处 《广东电力》 2011年第10期6-10,共5页 Guangdong Electric Power
基金 国家自然基金资助项目(51077081)
关键词 防冰 绝缘配置 冰闪试验 防冰涂料 anti-icing insulation disposition icing flashover experiment anti-icing coating
  • 相关文献

参考文献9

二级参考文献20

  • 1李鹏,范建斌,宿志一,罗真海.复合绝缘子表面憎水性和污秽对其湿闪电压的影响[J].中国电力,2005,38(4):50-53. 被引量:23
  • 2[6]Li Yu.Study of the influence of altitude on the characteristies of the electrical arc on polluted ice surface[D].Canada:Universite de Quebec a Chicoutimi,2002.
  • 3[7]Sun Caixin,Jiang Xingliang,Sima Wenxia,et al.Study of flashover performance and voltage correction of DC insulator in icing districts of altitude of 2500m and below[J].IWAIS 2002,Bmo,Czech Republic,2002.
  • 4[9]Phan L C,Matsuo H.Minimum flashover voltage of iced insulators [J].IEEE Transactions on Electrical Insulation,1983,(EI-18)6:605-618.
  • 5广东电网公司.广东电网公司2008年冰灾调查分析报告[R].广州:广东电网公司,2008.
  • 6广东省电力设计研究院.广东电网冰灾事故分析与应对措施研究[R].广州:广东省电力设计研究院.2008.
  • 7Chen Xing . Modeling of electrical arc on polluted ice surface[D]. Canada: University of Quebec in Chicoutimi, 2000.
  • 8Farzaneh M, Zhang J. Behavior of DC arc discharge on ice surface[C]. Proceedings of 8th international workshop on the atmospheric icing of structure, Iceland, 1998.
  • 9Cai-xin S, Xing-liang J, Wen-xia S, et al. Study of fiashover performance and voltage correction of DC insulator in icing districts of altitude of 2500m and below[C]. Proceedings of 10th IWAIS, Brno,Czech Repubic, 2002.
  • 10Jiang Xingliang, Sun Caixin, Sima Wenxia, et al. AC flashover performance and voltage correction of 27.5 and 110 kV iced composite insulator at atmospheric pressure of 4000~5500m high altitude districts[C]. IEEE Powercon'2002, Brno, Czech Repubic,2002.