直流变频热泵热水器系统性能的影响因素研究

Research on Performance Factors of Direct-current Variable Frequency Heat Pump Water Heater
下载PDF
导出
摘要 对R410a直流变频热泵热水器系统性能的影响因素进行了试验研究。结果发现:环境温度、进水温度不变时,在相同的水温温升区间内,压缩机以较高频率运行,膨胀阀保持相应的开度时,可以使系统的加热时间最短,耗电量最低。同时为了降低排气压力,随水温升高,压缩机频率应随之降低,电子膨胀阀应增大开度。另外,在环境温度22℃、进水温度20℃时,保持出水温度55℃以上,出水流量从1.8L/min增加到3.8L/min,系统制热量和COP随之增高,而且出水流量只有在3.0~4.0L/min时,系统才有最高的COP值,保持在4.0以上。 In this paper, performance factors of a R410a direct-current variable frequency heat pump water heater are experimentally studied. It is found that when ambient temperature and inlet water temperature are constant, compressor is worked at higher frequency and Electric Expansion Valve (EEV) is kept at a corresponding opening, the shortest heating time and the least power consumption of the system can be got at the same range of water temperature rise. At the same time, in order to reduce discharge pressure, compressor frequency should be reduced and EEV opening should be increased with water temperature increasing. In addition, at ambient temperature22℃ and inlet water temperature 20℃, outlet water temperature is kept above 55℃, When the outlet water flow is increased from 1.8L/min to 3.8L/min, the heat capacity and COP of the system are improved corresponding. And only when the outlet water flow is between 3.0 L/min and 4.0 L/min, the COP of the system can be achieved the maximum value and kept above 4.0.
出处 《建筑热能通风空调》 2011年第5期10-13,共4页 Building Energy & Environment
基金 广东省教育部产学研结合项目(2008B09050034)
关键词 直流变频 热泵热水器 压缩机频率 电子膨胀阀开度 出水流量 direct-current variable frequency, heat pump water heater, compressor frequency, electronic expansion valve opening, outlet water flow
  • 相关文献

参考文献6

二级参考文献20

  • 1石文星,田长青,王森.寒冷地区用空气源热泵的技术进展[J].流体机械,2003,31(z1):43-48. 被引量:11
  • 2凌勇坚.变频空调器的节电机理和实效[J].上海节能,2004(4):21-23. 被引量:2
  • 3吴甲斌.热力膨胀阀调节制冷剂流量的稳定性分析[J].交通部上海船舶运输科学研究所学报,1995,18(1):55-61. 被引量:6
  • 4宋红涛.[D].西安:西安交通大学,2001.
  • 5彦启森,石文星,田长青.空气调节用制冷技术.北京:中国建筑工业出版社,2005.
  • 6[4]Ghaleb Ali Ibrahim.Effect of Sudden Changes in Evaporator External Parameters on a Refrigeration System with an Evaporator Controlled by a Thermostatic Expansion Valve.International Journal of Refrigeration,2001,24:566-576
  • 7[5]Huelle Z R.The MSS Line-a New Approach to Hunting Problem.ASHRAE Journal,1972,(10):43-46
  • 8[7]Jongmin Choi,Yongchan Kimb.Influence of the Expansion Device on the Performance of a Heat Pump Using R407C under a Range of Charging Conditions.International Journal of Refrigeration,2004,27:378-384
  • 9[8]T P Castle,R N Richardson,T.J.Ritter.Thermostatic Valve Control Using a Non-Azeotropic Refrigerant,Isobutene/Propane Mixture.International Journal of Refrigeration.1999,(22):313-318
  • 10[9]J M Choi,Y C Kim.The Effects of Improper Refrigerant charge on the Performance of a Heat Pump with an Electronic Expansion Valve and Capillary Tube.Energy,2002,(27):391-404

共引文献62

相关作者

内容加载中请稍等...

相关机构

内容加载中请稍等...

相关主题

内容加载中请稍等...

浏览历史

内容加载中请稍等...
;
使用帮助 返回顶部