摘要 建立了带有闪发器的空气源热泵系统的数学模型,并对其进行性能模拟分析。模拟结果表明,在低温工况运行时,带有闪发器的空气源热泵系统的制热量和COP均高于传统单级压缩系统,且其排气温度低于传统单级压缩系统约20℃。采用节流前闪蒸补气策略有利于提高空气源热泵的低温运行可靠性和制热性能。 Mathematical model of air source heat pump system with flash-tank was developed and the system performance of air source heat pump system with flash-tank was studied by analyzing the simulation results.Results showed that the heating capacity and COP of air source heat pump system with flash-tank was larger and the discharge temperature of compressor was 20℃ lower than traditional air source heat pump when the system operated in low temperature condition.Using the flash-tank as economizer was good for the improvement of the air source heat pump's reliability and coefficient of performance in cold area.
出处 《流体机械》 CSCD 北大核心 2011年第11期81-87,共7页 Fluid Machinery
基金 广东省教育部产学研结合项目(2009B090300418)
关键词 闪发器 空气源热泵 数学模型 flash-tank air source heat pump mathematical model
  • 相关文献

参考文献6

  • 1董天禄.世界各国空气源热泵近期市场发展概况[J].制冷技术,2008,28(2):36-39. 被引量:5
  • 2柴沁虎,马国远.空气源热泵低温适应性研究的现状及进展[J].能源工程,2002,22(5):25-31. 被引量:120
  • 3James Brodrick. Energy Consumption Characteristics of Commercial Building HVAC Systems Volume III: Energy Savings Potential[ M ]. DOE, July, 2002.
  • 4A.E. Shah. A General Correlation for Heat Transfer during Film Condensation Inside Pipes [ J ]. Interna- tional Journal of Heat Mass Transfer, 1979,22 (4) : 547-556.
  • 5Turaga M, Guy R W. Refrigerant Side Heat Transfer and Pressure Drop Estimates for Direct Expansion Coil [J]. International Journal of Refrigeration, 1985, 8 (3) :134-142.
  • 6彦启森.空气调节用制冷技术[M].北京:中国建筑工业出版社,1983