某地下车库主通道为单向2车道,采用横向通风系统,换气次数按10次/h设计,补风量为排烟量的85%。排烟口尺寸0.8m×0.5m,距离地面3.5m,每25m设置一个。设置5MW的火灾,分两种排烟方案,使用CFX与FDS对烟气流动模拟计算。起火272s后主通道内人员疏散完毕,比较此时两种排烟方案下各防烟分区的温度分布、CO2浓度、风速矢量可知,方案二排烟效果优于方案一。在较大火灾情况下两种排烟方案控烟效果均不理想,建议限制通道内火灾荷载。
The main channel of an underground garage, two-way two-lane, has transverse ventilation system, the air changes 10 times per hour, and the make-up air is 85% of smoke ventilation. The exhaust port is 0.8 m×0.5 m of the size, 3.5 m from ground, set every 25 m. The smoke movement was simulated by CFX and FDS with 2 smoke exhaustion plans under 5 MW fire. The people in main channel can finish evacuation 272 s after the ignition, so the temperature distribution, concentration of CO2 and vector of wind velocity were compared under 2 smoke exhaust plans. The results showed that the plan 2 is better than plan 1. Restrict the fire load in channel was suggested since both of the plans were not good enough when the fire is bigger.
出处
《消防科学与技术》
CAS
北大核心
2011年第12期1137-1140,共4页
Fire Science and Technology
关键词
消防
地下车库
烟气控制
数值模拟
fire protection
underground garage
smoke control numerical simulation