期刊文献+

防风网对空冷岛换热效率的影响及防风网优化 被引量:3

Windshield on the Heat Transfer Efficiency of Direct Air Cooled Island and the Windshield Optimization
下载PDF
导出
摘要 以国内蒙达电厂600MW直接空冷机组为例,针对当前直接空冷机组运行中的突出问题——环境风的不利影响,利用CFD数值模拟软件Fluent,对空冷岛外部流场进行数值模拟。针对环境风的影响,在空冷岛挡风墙下延方向加装防风网。分析典型风向下,加装不同高度及开孔率的防风网对空冷岛换热性能的影响,从而对防风网进行优化。通过研究发现加装防风网后能有效地抵御环境风的影响,提高直接空冷岛的换热效率。 Taking Mengda 600MW direct air-cooled units in our country into consideration, in view of serious hurdles of air- cooled units available-the unfavorable influences of Ambient Wind, we tentatively proceeds to making numerical simulation research on external flow field of direct air-cooled island by using CFD software Fluent. For the case of affection by horizontal wind, installing windshield under the windbreak of air-cooled island. Under the typical wind direction, analyze the effect of different heights and different permeable rates of the windshield on the heat exchange efficiency for optimizing the windshield. Through the study , Fluent that after the installation of windshield can effectively resist the impact of environment wind and improve the heat efficiency of direct air-cooled island.
出处 《汽轮机技术》 北大核心 2011年第6期447-451,405,共6页 Turbine Technology
关键词 环境风 Fluent数值模拟 防风网 直接空冷岛 environment wind Numerical simulation of Fluent windshield direct air-cooled island
  • 相关文献

参考文献5

二级参考文献3

共引文献50

同被引文献35

  • 1张春发,谢飞,李永玲,张燕.漳山电厂300MW空冷机组热经济性状态方程[J].电力科学与工程,2005,21(2):64-66. 被引量:7
  • 2杨立军,杜小泽,杨勇平,刘登瀛.火电站直接空冷凝汽器性能考核评价方法[J].中国电机工程学报,2007,27(2):59-63. 被引量:72
  • 3Van Rooyen J A, Krfiger D G. Performance Trends of an Air - cooled Steam Condenser Under Windy Conditions [ J ]. Journal of Engineering for Gas Turbines and Power,2008,130 (2) :1 -7.
  • 4Bredell J R . Numerical Investigation of Fan Performance in a Forced Draft Air- cooled Steam Condenser[ D ]. Stellenbosch : Stel- lenbosch University.2005.
  • 5刘达.环境风对直接空冷凝汽器换热影响的研究[D].哈尔滨:哈尔滨工业大学,2011.
  • 6Van Rooyen J A. Performance trends of an air-cooled steam condenser under windy conditions [D]. Stellenbosch. StellenboschUniversity, 2007.
  • 7Meyer C J, Kroger D G. Numerical investigation of the effect of fan performance on forced draught air-cooled heat exchanger plenum chamber aerodynamic behavior [J]. Applied ThermalEngineering, 2004(24).. 359-371.
  • 8Bredell J R, Kroger D G, Thiart G D. Numerical investigation of fan performance .in a forced draft air- cooled steam condenser[J] Applied Thermal Engineering, 2006, 26(8-9): 846-852.
  • 9Duvenhage K, Kroger D G. The influence of wind on the performance of forced draught air-cooled heat exchangers [J]. Journal of Wind Engineering and Industrial Aerodynamics, 1996, 62(2-3): 259-277.
  • 10Meyer C J, Kroger D G. Air-cooied heat exchanger inlet flow losses[J]. Applied Thermal Engineering, 2001 (21): 771-786.