期刊文献+

城市污水处理A/A/O工艺中溶解氧的自动控制优化设计 被引量:3

Optimized Design of Automatic Control for Dissolved Oxygen in A/A/O Processes of Urban Sewage Treatment
下载PDF
导出
摘要 为了解决A/A/O工艺污水处理系统在进水负荷波动较大时曝气池中溶解氧(DO)的波动范围大的问题,该文以某A/A/O工艺的污水处理厂作为试运行系统,进行DO的自动控制优化研究,在传统的DO控制方法上加入曝气池的模型算法来进行DO控制的优化设计。试运行系统运行表明该控制方法可以使DO的控制精度范围达到±0.2 mg/L。 In order to solve the problem of large fluctuation of DO in aeration tank when large water load fluctuation in A/A/O process, a wastewater treatment plant of 200 000 m3/d was used to investigate the optimization of automatic control of A/A/O process. Adding algorithm of aeration tank model on the basis of the traditional system. Test run shows that the optimal control system can make the DO control accuracy range of ±0.2 mg/L.
出处 《净水技术》 CAS 2011年第6期70-73,共4页 Water Purification Technology
基金 北京市科技计划项目污水处理厂节能关键技术研究及示范(D101109047410001)
关键词 污水处理 溶解氧(DO) 自控优化 优化设计 曝气池模型算法 sewage treatment dissolved oxygen (DO) automatic control optimized design model algorithm of aeration tank