期刊文献+

提高不拆线测量500kV CVT介损及电容量准确度的方法 被引量:5

Improving Measurement Accuracy of Dielectric Loss and Capacitance of 500 kV CVT without Removing HV Lead
下载PDF
导出
摘要 不拆线试验是指在不拆除高压引线的情况下对电气设备进行预试,它的优点是可以减少工作量、增加安全系数、提高工作效率。为了降低拆除高压引线对设备造成的伤害以及提高检修效率,因此,运行维护单位大力推广在现场应用不拆高压引线的试验方法。针对500 kV叠装式CVT的结构特点,主要由电容分压器和电磁单元组成。介绍了不拆高压引线测量电容分压器的介损因数tanδ及电容量的新试验方法,分析了测量原理。通过与拆引线试验的数据对比,证明该试验方法是正确的。 Test without removing wire refers to pre-test of electrical equipment without removing lead and its advantage is in reducing amount of work,increasing safety factor and improving working efficiency.For reducing the equipment damage due to removal of HV lead and improving maintenance efficiency,the operation and maintenance utilities strongly recommend application of field test without removing HV lead.In view of structure feature of 500 kV integral type CVT consisting of capacitive voltage divider and electromagnetic unit.In this paper,a new method for testing dielectric loss and capacitance of capacitive voltage divider without removing high voltage(HV) lead is introduced and test principle is analyzed.Through comparison with the test data of removing HV lead,this method is proved to be correct.
作者 胡伟涛
出处 《电力电容器与无功补偿》 2011年第6期69-73,共5页 Power Capacitor & Reactive Power Compensation
关键词 电容式电压互感器(CVT) 不拆引线 介损因数tanδ 电容量 capacitor voltage transformer(CVT) HV lead not removed dielectric loss factor tanδ capacitance
  • 相关文献

参考文献12

二级参考文献41

共引文献44

同被引文献33

引证文献5

二级引证文献7

相关作者

内容加载中请稍等...

相关机构

内容加载中请稍等...

相关主题

内容加载中请稍等...

浏览历史

内容加载中请稍等...
;
使用帮助 返回顶部