变压器绕组轻微变形ns级脉冲响应分析法 被引量:16

Nanosecond Impulse Response Analysis on Transformers Winding Slight Deformation
下载PDF
导出
摘要 ns级脉冲响应分析法能够瞬时测取变压器绕组全频段下的响应特性,为促进它的实际应用,采用波前为5ns、脉宽为50ns的脉冲电压波作为激励信号,通过提高采样频率和采样点数,分频段去噪以获取具有较高频谱上限和精度的脉冲响应曲线。针对频响法对变压器绕组的轻微变形不灵敏的缺点,对5kV温升变压器和500kV电力变压器的高压绕组进行了不同程度的模拟轻微变形实验,并将频响法和ns级脉冲响应分析法的检测结果作了对比。实验结果证明该方法比频响法测试速度更快,精度更高,测取的频谱上限可达数十MHz。具有较高的灵敏度和重复性,能有效检测各种变压器绕组的轻微形变。 Nanosecond impulse response analysis method can instantaneously measure the whole spectrum response of transformer winding,and can obtain the impulse response curve that has higher upper frequency limit and accuracy by using pulse voltage wave which has 5ns's waterfront and 50ns's pulse width as the excitation signal.Consequently,we experimentally simulated different degrees of slightly deformation on the high voltage winding of 5 kV temperature-rising transformer and 500 kV power transformer in accordance with the characteristics that frequency response analysis is insensitive to transformer winding slightly deformation.Then we compared the results from frequency response analysis and nanosecond impulse response analysis respectively to detect the deformation.Experimental results show that nanosecond impulse response analysis has faster testing speed and higher accuracy than the frequency response analysis,and its upper frequency limit can reach tens of MHz,verifying that the method has higher sensitivity and reproducibility and can effectively detect the slight deformation in different kinds of transformers winding.
出处 《高电压技术》 EI CAS CSCD 北大核心 2012年第1期35-42,共8页 High Voltage Engineering
基金 国家重点基础研究发展计划(973计划)(2009CB724508) 国家创新研究群体基金(51021005)~~
关键词 ns级脉冲 脉冲响应 轻微变形 相关性分析 变压器 绕组 nanosecond pulse impulse response slight deformation correlation analysis transformer winding
  • 相关文献

参考文献20

  • 1李军,董立文,赵红.油浸式变压器的老化和寿命评估[J].高电压技术,2007,33(3):186-187. 被引量:34
  • 2王赞基,杨钰.大型电力变压器线圈中特快速暂态电压分布的计算[J].高电压技术,2010,36(4):918-925. 被引量:26
  • 3杜林,袁蕾,熊浩,唐纲,李刚,孙才新.电力变压器运行状态可拓层次评估[J].高电压技术,2011,37(4):897-903. 被引量:51
  • 4Dick E P,Erven C C. Transformer diagnostic testing by frequency response analysis[J]. 1978,97(6): 2144-22153.
  • 5DL/T911-2004.电力变压器绕组变形的频率响应分析法[S],2004.
  • 6Gharehpetian G B,Mohseni H,Moeller K. Hybrid modelling of inhomogeneous transformer windings for very fast transient over-voltage studies[J]. IEEE Transactions on Power Delivery, 1998,13(1) : 157-163.
  • 7Gharehpetian G B, Mohseni H, Gehnen M, et al. Resonance phenomena in inhomogenous transformer winding due to fast transi ents[C]// Proceedings of the 9th International Symposium on High Voltage Engineering. Graz,Austria: [s. n. ],1995.
  • 8Wang M, Vandermaar A J,Srivastava K D. Transformer winding movement monitoring in service key factors affecting FRA measurements [J]. IEEE Electrical Insulation Magazine, 2004, 20(5): 5-12.
  • 9Abeywickrama K G N B, Serdyuk Y V, Gubanski S M. Explo ring possibilities for characterization of power transformer insu lation by frequency response analysis (FRA)[J]. IEEE Trans actions on Power Delivery, 2006,21(3):1375-1382.
  • 10王有元,龚森廉,廖瑞金,李剑,何志满.电力变压器油纸绝缘可靠性与老化特征参量间的相关性[J].高电压技术,2011,37(5):1100-1105. 被引量:30

二级参考文献203

共引文献315

同被引文献188

引证文献16

二级引证文献148

相关作者

内容加载中请稍等...

相关机构

内容加载中请稍等...

相关主题

内容加载中请稍等...

浏览历史

内容加载中请稍等...
;
使用帮助 返回顶部